3. The Create Network Variable dialog box opens. Enter the name, number, and type of the

dynamic network variable(s) you are creating.

a. Enter the name of the dynamic network variable. This name must be unique within the

functional block. It may be up to 85 characters long and may include embedded spaces, but it
may not include period, backslash, colon, forward slash, or double quote characters.

b. Enter the number of dynamic network variables you are creating.

c. If you are creating more than one dynamic network variable, IzoT Commissioning Tool will

automatically append an index, starting at 1, to the second dynamic network variable. IzoT
Commissioning Tool will then increment the index for each additional dynamic network
variable you are creating. For example, if the dynamic network variable name is “mynv” and
you are creating three network variables, the names will be “mynv”, “mynv1”, and “mynv2”.

If you are creating 10 or more network variables, you should append a “01” to the dynamic
network name (for example, mynv01). If you are creating three network variables, the names
will be “mynv01”, “mynv02”, and “mynv03”. This ensures that the dynamic network
variable names will be listed in numerical sequence in various IzoT Commissioning Tool
menus and reports.