Design overview, Defining network requirements and organization, Selecting a network installation scenario – Echelon IzoT Commissioning Tool User Manual

Page 43: Engineered system scenario

Advertising
background image

Design Overview

To prepare to design an IzoT Commissioning Tool network, follow these steps:

1. Define network requirements and organization.
2. Select a network installation scenario.
3. Determine user permissions for viewing and changing the network.
4. Optimize network performance.

Defining Network Requirements and Organization

You can define your network’s requirements by evaluating which devices (sensors, actuators, and
controllers) are needed to achieve the desired network functions and how the devices will be integrated
into the network. For example, your network may need a simple fan coil unit, which could require a
fan start/stop relay, a cooling coil valve, and a supply air temperature sensor. You could use digital
output, analog output, and analog input devices, respectively, to integrate these devices (the analog
output module could also includes a PID controller you can use to control the fan coil unit).

Once you define the network requirements, you can figure out how to organize the network in IzoT
Commissioning Tool. You can help organize the network by answering the following questions:

• How will devices and functional blocks be grouped within subsystems?
• Which functional blocks are needed for the devices to accomplish desired tasks?
• How do functional blocks need to be configured and connected to correctly interpret values from

sensors, perform any necessary calculations, and drive actuators?

Selecting a Network Installation Scenario

You can design your entire network without commissioning any devices until after your design is
complete, or you can design your network and commission devices at the same time. These two
approaches are called installation scenarios. The first network installation scenario is called the
engineered system and the second is the ad-hoc system. You can use both scenarios within a single
system, or you can use either exclusively. The best scenario for a given network depends on many
factors including the skill level of the installer, desired flexibility for the network, and the end-user
requirements.

Engineered System Scenario

The engineered system scenario allows you to design the network without having access to the
physical devices

First, you design the network offsite using IzoT Commissioning Tool. You drag IzoT Commissioning
Tool SmartShapes representing devices, routers, IP-852 routers, functional blocks, and connections
from an IzoT Commissioning Tool stencil to an OpenLNS CT drawing and arrange them on the
drawing, and into multiple subsystems if desired.

Once you are onsite and have attached an IzoT Commissioning Tool computer to the network, you
then commission the physical devices. IzoT Commissioning Tool commissions a device by
configuring the physical device to match the configuration that you specified in the OpenLNS CT
drawing.

Engineered systems must often be modified during on-site installation due to differences between
as-drawn plans and the physical network. IzoT Commissioning Tool supports on-site changes to the
engineered system to allow for these changes during commissioning.

The advantage of the engineered system scenario is that it makes network installation quick, easy, and
error-free because most of the time-consuming data entry and processing is done offsite during the
design phase. This scenario is often used for building and industrial automation systems, in which the
original design closely matches the actual installation.