3. Choose the synchronization operation(s) you want to perform by selecting the following options.

OpenLNS Database

The network database resynchronization options are only available if
IzoT Commissioning Tool is running on the same computer as the
OpenLNS Server.

Validate OpenLNS
Database

Validates the structure of the OpenLNS network database.

Validate and Repair
OpenLNS Database

Validates the structure of the OpenLNS network database and
repairs the database if any errors are detected.

L

ON

W

ORKS

Network

Synchronize Network
to Database
(recommission
devices)

Commissions the physical devices in the L

ON

W

ORKS

network to

make them consistent with the OpenLNS network database. To use
this option, IzoT Commissioning Tool must be OnNet.

Update Location
Path and ID in
Devices

Stores the current subsystem path in the SCPTlocation
configuration property of application devices that have a
SCPTlocation configuration property, and stores the current
subsystem ID in the Location field of application devices and
routers. This option is only available if at least one of the check
boxes in the Network Properties: Recovery options category is
selected.

If an application device and its functional blocks span multiple
subsystems, IzoT Commissioning Tool updates the SCPTlocation
configuration property with the subsystem path in which the device
SmartShape is located.

The subsystem ID is the first 15 bits of the OpenLNS subsystem
handle (in a very large network with many subsystems where more
than 32,767 subsystems have been created and deleted, this could
result in multiple unique subsystems having the same ID; however,
this is very unlikely).