Subsystem recovery options – Echelon IzoT Commissioning Tool User Manual

Page 240

Advertising
background image

3. Verify that the recovered network opens to be correct. The recovery wizard logs the recovery

tasks as well as any errors that occurred in the detailed recovery log. A trace log lists the steps,
with the times and dates, that the wizard took to recover the database. You can view the logs after
the database has been recovered. These logs are useful for tracking any errors that the recovery
process encounters, such as connection errors or lost data.

4. To actively manage the recovered network, change the management mode to OnNet. To do this,

click Add-ins, point to LonWorks Network, and then click Network Properties. Click the
Network Interface tab, select OnNet under the Management Mode box, and then click OK.

The following sections detail each of these steps. The subsystem recovery options that you can set in
an IzoT Commissioning Tool network design are also described. These subsystem recovery options
help you recover your network in the event you lose the network design and all backups.

Subsystem Recovery Options

You can make your IzoT Commissioning Tool network designs easier to recover and enhance a
recovered network design by storing recovery data in the physical devices. You can store the
subsystem ID of a device in its location string and its subsystem path in its SCPTlocation
configuration property (if it has one). This recovery data is not part of the network configuration of a
device.

When you recover a network, the following data is used in the listed order:

1. Subsystem path stored in a CSV file.

2. Subsystem path stored in a SCPTlocation configuration property that is associated with the Node

Object, if present, or associated with the application device.

3. Subsystem ID stored in the location property (the most-significant bit of the first byte of the

location string must be set).

4. The Recovered subsystem. A device is placed in a subsystem named “Recovered” if a CSV file

is not imported or subsystem data is not included in the file, and the device does not have a valid
subsystem ID or a valid SCPTlocation configuration property

By default, both subsystem recovery options are enabled in new networks. For IzoT Commissioning
Tool network designs created with previous versions of IzoT Commissioning Tool, they are disabled.
To enable the subsystem recovery options and update existing devices in a network, follow these steps:

1. Click Add-ins, point to IzoT Commissioning Tool, and then click IzoT Commissioning Tool

Options. The Network Properties dialog opens.

2. Select Recovery in the Options Category list.

3. Select the check boxes under the Subsystem Recovery Options box. This will enable subsystem

location data to be stored and updated in all future application devices and routers you create.