• A value of 0 indicates no.
• A value of 1 indicates yes.
• A value of 2 indicates that the IzoT Commissioning Tool user

will be prompted.

The default value is 2 to prompt the user.

ChanTypeList

A semicolon-separated list of valid channel type IDs for the
device. A value of -1 in the list indicates that the user has the
option of selecting from all channels in addition to the channels of
the specific types defined. Channel type IDs correspond to the
ChannelTypeNumber values contained in the StdXcvr.xml file
available from www.lonmark.org/spid. By default, all channel
types are allowed.

EditAdvPropCap

Specifies handling of the advanced properties tab in the device
properties dialog.

• A value of 0 specifies that the advanced properties dialog is

not to be displayed.

• A value of 1 indicates that the advanced properties dialog is

to be displayed, but cannot be modified.

• A value of 2 indicates that the advanced properties dialog is

displayed and changes can be made.

The default value is 2 (the advanced properties dialog is displayed
and changes are allowed).

EditPropCap

Specifies handling of the basic properties tab in the device
properties dialog.

• A value of 0 specifies that the basic properties dialog is not to

be displayed.

• A value of 1 indicates that the basic properties dialog is to be

displayed, but cannot be modified.

• A value of 2 indicates that the basic properties dialog is

displayed and changes can be made.

The default value is 2 (the basic properties dialog is displayed and
changes are allowed).

FbModes

Specifies a semicolon-separated list of the scopes for each of the
functional blocks in this device. This cell’s data must be ASCII
text in the format <scopeSelector0>;<scopeSelector1>;... where
scopeSelector0 applies to the functional block with index 0 (the
Node Object), scopeSelector2 applies to the functional block with
index 1, and so on. You can see what functional block in a device
has what index by right-clicking the device, selecting Properties
from the shortcut menu, and clicking the Functional Blocks tab of
the device properties dialog.

If this cell is not specified, IzoT Commissioning Tool uses scope
0 for functional profile numbers 1–19999, and scope 3 for all
other functional profiles. This means that functional block
SmartShapes based on user functional profiles with numbers of
20000 and above, as well as all inherited profiles, must either set
this value or must include a plug-in that sets the appropriate
value.