6. Select the desired synchronization options and subsystem assignments.

Create Shapes for all
Connected NVs/MTs

Adds SmartShapes to functional blocks for all connected
network variables or message tags created by the
resynchronization.

If this check box is cleared, IzoT Commissioning Tool will use
generic connections when possible. It will still create network
variable or message tag SmartShapes for connections to
supernodes and for those functional blocks that already contain
network variable or message tag SmartShapes.

Use Reference Shapes for
all Connections

Represents all network variable connections created by the
resynchronization with reference connection SmartShapes.

If this check box is cleared, IzoT Commissioning Tool will use
standard connection SmartShapes for connections for network
variable hubs and targets located in the same subsystem.
Reference connection SmartShapes are always used for
connections that span subsystems.

Automatically Drop
Device, FB, and
Subsystem Shapes

Automatically adds SmartShapes to the drawing for all devices,
functional blocks, and subsystems created by the
resynchronization.

If this check box is cleared, IzoT Commissioning Tool will
prompt the user to select whether a SmartShape should be added
for a device, functional block, or subsystem created by the
resynchronization.

Minimize Drawings
during Resync

Minimizes all the drawings in the IzoT Commissioning Tool
network during the resynchronization. This speeds up the
resynchronization as it reduces the time Visio spends updating
the drawings.

Check for Connections
for Missing FB Shapes

Enables IzoT Commissioning Tool to check for connections to
functional blocks that are in the OpenLNS database but not
represented by a SmartShape in the OpenLNS CT drawing.

Subsystem to Visio
Document Assignment

Select in which Visio drawing file to place the subsystems in
your network. You have four choices:

Single Visio Document for all Subsystems. Places all

subsystems in a single Visio document.

Prompt for Subsystem Document Assignment. Prompts

you to specify the Visio document for each subsystem.

Separate Document for each Subsystem Hierarchy

below Root. Places each subsystem hierarchy below the
top-level subsystem in a separate, new Visio document.

Custom. Opens the Subsystem Document Assignment

dialog. In this dialog, you specify the Visio document for
each subsystem.

7. Click Next. If you selected the Automatically Drop Device, FB, and Subsystem Shapes check

box, the Select Stencil dialog box opens. If you cleared this check box, skip to step 9.