Recovery Options

The Recovery options category lets you store and automatically update subsystem data in application
devices and routers. This is useful in the event you need to recover your OpenLNS network database
from the network. Setting these options enables IzoT Commissioning Tool to use the saved subsystem
data to place application devices and routers in their correct subsystems. See Recovering an IzoT
Commissioning Tool Network
in Chapter 7, Maintaining Networks, for more information on the
network recovery process.

The Recovery category contains the following options. The changes you make in the Recovery
options category are applied to the current network on all IzoT Commissioning Tool computers.

Subsystem Recovery
Options

If you select either of the following subsystem recovery options in
the OpenLNS CT drawing, you need to resynchronize your
drawing and select the Update Location Path and ID in Devices
check box in the Synchronize OpenLNS CT Drawings dialog
box in order to update the devices with the current subsystem
location data.

To resynchronize your drawing, click Add-ins, point to
Synchronization, and click Resynchronize.

Set SCPT Location
Value to Subsystem
Path

Stores the subsystem path in the SCPTlocation configuration
property of an application device when it is created. Automatically
updates SCPTlocation when the application device is
commissioned. The SCPTlocation configuration property must
apply to the Node Object functional block if the device has a Node
Object functional block, or it must apply to the entire device if the
device does not have a Node Object functional block.

Automatically updates the SCPTlocation

configuration property

when the application device is moved or its subsystem is moved or
renamed (provided that the

Update all Devices when Subsystem

Name is Modified option is set to Yes)

, or you select the

Update

Location Path and ID in Devices check box in the Synchronize

IzoT Commissioning Tool User’s Guide

341

Advertising