Section 3

Auto-Zone Plus

3-16

Programming

Zone Manager

Configuration

These configuration setpoints are normally entered only one time and then never accessed
again. This is why they occupy their own menu location, so the user is not required to step
through these during normal setpoint Read and Reset.

Note: On initial power up, the system must be configured before it can be

successfully operated.

Configuration Screen #1








Caution: The zones should be consecutively addressed with no skipped address

locations. If you do skip an address, the Zone Manager will presume
there is a missing zone, and an alarm will occur.





ZONE POLLING RANGE

First Zone Addr: 1

Last Zone Addr: 1

[0 = RA Control]

The Zone Manager needs to know the address range of the
attached Zone Controllers to be polled
. The user enters the
addresses of the first and last zones here. If you are controlling
from Return Air Temperature instead of voting zones, input –1
for both the first and last address.

Minimum Default Maximum

First Zone
Addr

1 1 16

Last Zone Addr

1

1

16