Status screen #1, Status screen #2, Status screen #3 – Auto-Zone Control Systems Auto-Zone Plus Systems Installation & Operation (Version 03A) User Manual

Page 117

Advertising
background image

Auto-Zone Plus

Section 3

Programming

3-31

Status Screen #1



Status Screen #2


Note: If slide adjust is set for 0

°, the pushbutton override will not function.

Status Screen #3











Note: On Pressure Independent zones, cfm will be substituted for the word Setpt or

the % symbol.

Zone # 1 v4.xx

Occupied Mode

Voting Unit

Line 2 - Unoccupied Mode

Occupied Mode
Pushbutton Override
Force Mode Active!

Line 3 - Voting Unit

Non-Voting Unit

Zone # 1 v4.xx

Temperature: 75.4°F

CSP 75.0° HSP 72.0°

Slide Adjust.: 0.0°

Line 2 - Current Zone Temperature

Line 3 - Current Cooling Setpoint (CSP) & Heating

Setpoint (HSP)

Line 4 - Optional Sensor Slide Adjust (located on Zone

Wall Sensor) effect on current operating Setpoints.

Zone # 1 v4.xx

Damper Pos 20%

Minimum Setpt 20%

Maximum Setpt 100%

Line 2 - Current Zone Damper Position in the percentage it

is open for pressure dependent dampers, for
pressure independent, the damper position and the
CFM will be displayed.

Line 3 - Currently active Minimum Damper/Airflow

Setpoint. Each mode has its own minimum
setpoint. These are Vent Mode, Cooling Mode,
Heating Mode and Nite Mode.

Line 4 - Currently active Maximum Damper/Airflow

Setpoint. This value is user adjustable, but it is
used in all modes of operation, unlike the
Minimum Damper/Airflow Setpoint.