4 zone manager bypass damper wiring checks, Figure 4-11: bypass actuator troubleshooting – Auto-Zone Control Systems Auto-Zone Plus Systems Installation & Operation (Version 03A) User Manual

Page 186

Advertising
background image

Section 4

Auto-Zone Plus

4-36

Start-Up and Troubleshooting

2.3.4

Zone Manager Bypass Damper Wiring Checks

Meter Should Measure Approximately

5000 Ohms With Actuator In Middle

Of Full Travel Position. See Item #3 Below

For Instructions.

+

-

Bypass

Actuator

OE512, OE741 & OE282-02 Bypass Damper Package

Zone Manager Board

Transformer

PWR

V4

V3

CLOSE

OPEN

FDBK

GND

GND

24VAC

NE5090

Line

Voltage

GND

24VAC

Actuator Clutch

Modular Cable

Bypass Damper Components & Wiring

Power Connection Terminal

Jumper Wire Between

24VAC And Open Or Close

Terminal As Required

Jumper Wire

Between 24VAC

And Ground

Remove Terminal Plug

From Zone Manager Board

When Performing Jumper

Testing Of Actuator

Bypass Damper

Terminal Plug

Bypass Damper

Terminal Socket

FDBK

OPEN

GND

GND

PJ1

PJ2

LD

2

LD

1

OPEN

CLOSE

CLOSE

TB1

TB2

(PL101824) BYPASS AND

SLAVE INTERFACE CARD

1.) Confirm That All Wiring Is Correctly

Connected To The Bypass & Slave

Interface Card Terminals And The Zone

Manager Bypass Actuator Terminals. Be

Sure The Modular Cable Is Plugged In To

Both The Actuator And The Modular Plug

Labeled "To Actuator" On The Bypass &

Slave Interface Card. If No Wiring Errors

Are Found, Proceed To The Next Step.

2.) Remove Communications Wiring From

The Zone Manager Board Then Remove

The Power From The Zone Manager

Board. Go To The Bypass Damper

Location And Depress Clutch On The

Actuator. Rotate The Actuator Clamp And

Damper Shaft Back And Forth. Check To

Verify That The Damper Moves Freely

From Full Open To Full Closed Position.

Check For Binding Or Interference That

Prevents Full Opening And Closing Of The

Bypass Damper. If The Damper Appears

To Move Freely Proceed To The Next Step.

3.) Depress The Clutch On The Actuator.

Rotate The Damper Shaft To The Middle Of

The Actuator

(See

Drawing Above For Middle Of Full Stroke

Position Picture). Connect The Meter

Between The Ground And Feedback

Wires On The Bypass & Slave Interface

Card As Shown Above. Meter Should Read

Approximately 5000 Ohms. If The Meter

Does Not Read Approximately 5000 Ohms,

Recheck The Wiring. If No Wiring Errors

Are Found The Problem Is Probably A Bad

Actuator Or Modular Cable.

Full Stroke Position

4.)

5.) Remove The Bypass Damper Terminal

Plug From The Bypass Damper Terminal

Socket On The Zone Manager Board As

Shown Above. Run A Jumper Wire From

The 24VAC Power Connection On The

Zone Manager Board To The “Open”

Terminal On The Bypass Damper Terminal

Plug And A Jumper From The GND

Connection On The Zone Manager Board

To The GND Terminal On The Bypass

Damper Terminal Plug.

Disconnect The Jumper Wire From The

“Open” Terminal At The Bypass Damper

Terminal Plug And Connect The Jumper

From 24VAC To The “Close” Terminal On

The Bypass Damper Terminal Plug.

Go To The Bypass

Damper Location To Confirm That The

Damper Moves Towards Its “Closed”

(Counterclockwise) Position. If The

Actuator Drives In Only One Direction Or

Doesn’t Drive In Either Direction It Is

Probably A Bad Actuator Or Modular Cable.

If It Drives Open And Closed In The Jumper

Test Just Performed But Not When

Connected To The Zone Manager Board,

The Problem Is Probably The Zone

Manager Board.

Reconnect Power To The Zone

Manager Board. The Damper Actuator

Should Start Its Calibration Procedure And

Move To Its Full Open (Clockwise) Position

And Then To Its Full Closed

(Counterclockwise) Position. If The Damper

Actuator Does Not Move Through Its Full

Calibration Range Proceed To The Next

Step.

The Green Light On

The Bypass/Slave Interface Card should

Glow. Go To The Bypass Damper Location

To Confirm That The Damper Moves

Towards Its “Open" (Clockwise) Position.

The

Red Light On The Bypass/Slave Interface

Card should Glow.

6.) If You Have Another Actuator Motor

Of The Same Type (One Can Be

Borrowed From Another Zone Or Bypass

Damper), You Can Try Switching Out The

Original Actuator And Using The

Borrowed Actuator To Verify Operation.

Disconnect The 24VAC Power From The

Zone Manager Board. Remove The

Jumper Wire That Was Used In The

Previous Checkout Step. Reconnect The

Bypass Damper Terminal Block To The

Zone Manager Board. Reconnect The

24VAC Power To The Zone Manger

Board.

Replace The Defective Actuator With A

New Actuator.

The Damper Actuator Should

Start Its Calibration Procedure And Move

To Its Full Open (Clockwise) Position And

Then To Its Full Closed

(Counterclockwise) Position. If The

Borrowed Damper Actuator Moves

Through Its Full Calibration Range

(Shown With Actuator

In Middle Of Full Stroke)

Figure 4-11:

Bypass Actuator Troubleshooting

Advertising