Supply air temperature sensor, Return air temperature sensor – Auto-Zone Control Systems Auto-Zone Plus Systems Installation & Operation (Version 03A) User Manual

Page 72

Advertising
background image

Section 2

Auto-Zone

Plus

2-40

Design

Guide

Supply Air Temperature Sensor

The supply air temperature sensor should be located as close to the rooftop unit
discharge as possible for best response. It should also be mounted upstream of the bypass
damper for best results. Locate the sensor in the center of the widest part of the duct. Use
the supplied template and a 5/16" drill to make a hole for the sensor. Install the gasket
over the probe and mount securely to the duct using the supplied sheet metal screws. Be
sure the gasket is compressed to provide an air tight seal. For best accuracy, apply
insulation on the outside of the duct, over the sensor. This will help prevent thermal
gradients from affecting the sensor.

Figure 2-29:

Supply or Return Air Sensor Installation

Return Air Temperature Sensor

The return air temperature sensor should be located as close to the rooftop unit return
air intake as possible. Avoid locations which will be exposed to extreme outside
temperatures. Locate the sensor in the center of the widest part of the duct. Use the
supplied template and a 5/16" drill to make a hole for the sensor. Install the gasket over
the probe and mount securely to the duct using the supplied sheet metal screws. Be sure
the gasket is compressed to provide an air tight seal. For best accuracy, apply insulation
on the outside of the duct, over the sensor. This will help prevent thermal gradients from
affecting the sensor.

Caution:

Do not mount the return air sensor in the mixed air section. This will

cause an error in the reading.

Mounting Plate

Gasket

Adhesive Backed Drill Guide
Mounting Template

11-1/2" (OE231)

5-1/2" (OE230)

Mounting Plate

4.0"

3/4"

1/4" Hex Head Sheet Metal Screws

Thread
Together

Duct Work

Drill 5/16" Hole In Ductwork For Probe

Leads Are Non-polarized.
Butt Splice Leads To 24 Gauge
Wire Minimum. Connect Leads
To "Analog In" And "Ground"
At Controller.