Auto-Zone Control Systems Auto-Zone Plus Systems Installation & Operation (Version 03A) User Manual

Page 71

Advertising
background image

Auto-Zone Plus

Section

2

Design Guide

2-39

Tip:

Be careful when cutting the hole for the sensor or the plastic bezel of the sensor
may not completely cover the opening.


Tip:

If sensors must be installed on walls which are solid and cannot be penetrated,
surface mounted boxes and raceway can be purchased from your local electrical
distributor.


Connect the terminal labeled GND on the room sensor to the terminal labeled GND on
the Zone Controller terminal block for the TEMP SENSOR. See Figure 2-27. Connect
the terminal labeled TMP on the room sensor to the terminal labeled TEMP on the Zone
Controller terminal block for the TEMP SENSOR. If the room sensor has a setpoint
adjust slider, connect the sensor terminal labeled AUX to the Zone Controller AUX
terminal block labeled AUX1.

Figure 2-27:

Room Sensor to Zone Controller Wiring


Connect the terminal labeled GND on the room sensor to the terminal labeled GND on
the CV Controller terminal block for the TEMP SENSOR. See Figure 2-28. Connect the
terminal labeled TMP on the room sensor to the terminal labeled AIN1 on the CV
Controller terminal block for the TEMP SENSOR. If the room sensor has a setpoint
adjust slider, connect the sensor terminal labeled AUX to the CV Controller AUX
terminal block labeled AIN2.

Figure 2-28:

Room Sensor to CV Controller Wiring

GND

AUX

TMP

OVR

R

E

L

O

C

R

E

M

R

O

A

W

Room Sensor

Zone Controller

AUX

TEMP

GND

GND

AUX1

+VS

AUX2

TB2

++

TB1TB1

Connection To AUX
Terminal Required Only
When Sensor Is Specified
With Slide Adjust Option

Advertising