Section 4

Auto-Zone Plus

4-12

Start-Up and Troubleshooting

1.3.3

Checking the CommLink IV Driver

Diagram

Set Your Meter

To Read DC Volts

+

-

+

-

+

-

T-To-G

+3.1 VDC

To

+3.2 VDC

R-To-G

+3.4 VDC

To

+3.6 VDC

Communications

Loop

Disconnected

CommLink IV

To 24 VAC

Power Supply

MODEM

RS-232

Serial #

COMPUTER

USB

10/100

ETHERNET

DIAG

24V

T

T

G

G

R

R

GN

D

485 LOOP

485 LOOP

POWER

ACT

LNK

USB

Co

n

fi

g

No

rm

al

Overview

This test checks for proper Network loop voltages coming from the CommLink IV.

Tip: The Loop LED (located on the front panel) should “flicker” when the CommLink IV

is attempting to communicate. The Loop LED will flicker more noticeably for a few
seconds when first powered up. If the LED does not flicker, the unit is not
functioning.

Proper loop voltages are essential for reliable communications. It is normal to see
fluctuations at this point on the CommLink IV. The average value should be close to the
acceptable range described below. Values will vary upon initial powerup for about 10-15
seconds as the unit attempts to communicate.

Measurements

Local Loop

Acceptable Range

T - G (SHLD)

3.1 – 3.2 Volts DC

R - G (SHLD)

3.4 – 3.6 Volts DC

Action

Condition Action

If voltages are too high or too low on either
side

1. The CommLink IV has a damaged
comm driver chip. Replace the
CommLink IV.
The driver chip is not
field replaceable.