Minimum default maximum, Setpoint screen #15, Setpoint screen #16 – Auto-Zone Control Systems Auto-Zone Plus Systems Installation & Operation (Version 03A) User Manual

Page 113

Advertising
background image

Auto-Zone Plus

Section 3

Programming

3-27

Setpoint Screen #15




Setpoint Screen #16







Once a heating or cooling stage is activated, the Supply Air
must change accordingly by 5

° before this amount of time

elapses, or a mechanical failure is assumed and an alarm is
generated.

Minimum Default Maximum

Alarm Delay

0 Min.

30 Min.

300 Min.

SUPPLY AIR SETPOINTS

Alarm Delay Period

Mechanical Failure

Detection: 30 Min

If you have a more accurate digital thermometer that doesn't
agree with the current temperature readings of one or more of
your sensors, these Type III Thermistor sensor readings can be
calibrated.

Enter a positive number if the current reading is too low.

Enter a negative number if the current reading is too high.

The OAT calibration only applies to the controller that has the
Outdoor Sensor installed. It has no effect on the global
broadcast value of the outdoor air temperature.

Minimum Default Maximum

Supply Sensor SAT

-100.0°F

0.0°F

+100.0°F

Return Sensor RAT

-100.0°F

0.0°F

+100.0°F

Outdoor Sensor OAT

-100.0°F

0.0°F

+100.0°F

Sensor Rdg Offset

SAT.: 82.9° 0.0°

RAT.: 77.2° 0.0°

OAT.: 70.2° 0.0°