Section 3
Auto-Zone Plus
3-48
Programming
Setpoint Screen #15
Sensor Rdg Offset
ZNT.: 73.6 0.0
SAT.: 76.5 0.0
OAT.: 70.2 0.0
As described in the Zone Controller section, the Thermister
Type III Sensor readings can be calibrated. The Outdoor Air
calibration offset only applies to the CVAHU that has the
sensor installed. It has no effect on the Global Broadcast value
of Outdoor Air.
Minimum Default Maximum
Zone Sensor ZNT
-100.0°F
0.0°F
+100.0°F
Supply Sensor SAT
-100.0°F
0.0°F
+100.0°F
Outdoor Sensor OAT
-100.0°F
0.0°F
+100.0°F