Auto-Zone Plus

Section 4

Start-Up and Troubleshooting

4-27


COOL2 - (Y2) The Zone Manager will make the connection to the “R” terminal
when activating the second stage of cooling.

HEAT1 - (W1) The Zone Manager will make the connection to the “R” terminal
when activating the first stage of heating.

HEAT2 - (W2) The Zone Manager will make the connection to the “R” terminal
when activating the second stage of heating.

2.2.4 Economizer/VFD

Connector

This connector has two control signal outputs. The A1 terminal is used for control of an
Economizer Actuator. The A2 terminal is used for control of a Variable Frequency Drive
(VFD).

A1 - This analog output provides a 0-10 VDC, 2-10VDC, 10-0 VDC or 10-2
VDC configurable control signal, which modulates the Economizer Damper
motor position.

A2 - 0-10 VDC, 2-10VDC, 10-0 VDC or 10-2 VDC configurable control signal,
which modulates a Variable Frequency Drive (When VFD is used instead of
Bypass Actuator & Damper for Duct Static Pressure Control)

Warning:

This output must not be shorted to 24 VAC. Some actuators have
this wiring set-up. When an actuator has this type of wiring, the
Economizer motor must be powered from a separate isolated 24 VAC
transformer to avoid damaging the Zone Manager. Belimo actuators
do not have this problem and may be wired without an isolation
transformer.

GND - Common return wire, this point is tied to GND on the Zone Manager.

2.2.5 Powered

Exhaust

This connector provides a normally open set of isolated contacts, which CLOSE when the
Economizer is driven open past its minimum position setpoint. The wiring consists of two
wires, which are interchangeable.