Zone Controller Setpoints


Note: The top line always displays the currently selected Zone Controller and the

controller type.


PD ZONE ADDRESS

means a Pressure Dependent Zone is selected.

PI ZONE ADDRESS

means a Pressure Independent Zone is selected.

Setpoint Screen #1








Setpoint Screen #2





PD ZONE ADDRESS 1

OCCUPIED SETPOINTS

Cooling Setpt: 75°F

Heating Setpt: 72°F

The Occupied Heating and Cooling Setpoints are entered on
this screen. The Heating Setpoint should always be two
degrees below the Cooling Setpoint, or the Zone Controller
will not accept the new values. The System Manager can't
prevent the entry of invalid setpoints. If invalid setpoints are
entered, the previous settings will be retained by the system and
displayed the next time the Zone Setpoints are accessed.

Minimum Default Maximum

Cooling Setpoint

50°F

75°F

90°F

Heating Setpoint

50°F

72°F

90°F

PD ZONE ADDRESS 1

UNOCCUPIED SETPOINTS

Cool Setup...: 10°F

Heat Setback.: -10°F

The Unoccupied Heating and Cooling Setback values are
entered on this screen. The Occupied Cooling Setpoint will be
increased by the Cooling Setback during Unoccupied Mode
and the Heating Setpoint will be decreased by the Heating
Setback.

Minimum Default Maximum

Cool Setup

0°F

10°F

30°F

Heat Setback

0°F

-10°F

-30°F