Section 1

Auto-Zone Plus

1-24

Design Guide

Rectangular Zone Dampers

The Rectangular Damper is used in applications where rectangular ducts are specified or
required because of space limitations or job requirements. The Rectangular Damper
utilizes opposed blades for improved air flow control. See Table 1-4 for sizing info.
























Table 1-4:

Rectangular Damper Sizing Information

Rectangular Damper Selection Data

Height

(B)

8

10

12

14

16

18

20

22

24

26

28

30

32

34

36

Width

(A)

Airflow Through Rectangular Damper

CFM @ 1000 FPM Velocity

8

410 530 640 740 850 970 1080 1190 1300 1410 1520 1630 1740 1850 1970

10

510 590 690 800 910 1030 1150 1260 1380 1500 1610 1730 1840 2000 2080

12

560 650 730 850 970 1090 1210 1330 1460 1580 1700 1820 1940 2060 2190

14

660 770 880 1030 1180 1330 1480 1630 1760 1910 2060 2210 2360 2510 2640

16

750 890 1030 1200 1370 1540 1710 1880 2060 2230 2400 2570 2740 2910 3090

18

770 980 1180 1380 1580 1780 1980 2180 2350 2550 2750 2950 3150 3350 3540

20

850 1090 1330 1550 1770 1990 2210 2430 2650 2870 3090 3310 3530 3750 3990

22

930 1210 1480 1730 1980 2230 2480 2730 2950 3200 3450 3700 3950 4200 4440

24

950 1290 1630 1900 2170 2440 2710 2980 3250 3520 3790 4060 4330 4600 4880

26

990 1390 1780 2080 2380 2680 2980 3280 3550 3850 4150 4450 4750 NA

NA

28

107

0

1500 1930 2250 2570 2890 3210 3530 3850 4170 4500 4820 NA

NA

NA

30

102

0

1550 2080 2430 2780 3130 3480 3830 4150 4500 4850 NA

NA

NA

NA

32

109

0

1660 2230 2600 2970 3340 3710 4080 4450 4820 NA

NA

NA

NA

NA

34

115

0

1770 2380 2780 3180 3580 3980 4370 4750 NA

NA

NA

NA

NA

NA

36

106

0

1790 2520 2670 3090 3510 3930 4350 5040 NA

NA

NA

NA

NA

NA

Notes:

1.) Zone Dampers should be sized based on the required zone CFM. The table above is calculated based on 1000 FPM velocity through
the Rectangular Damper. Zone Damper recommended velocity is 1000 - 1500 FPM. Select 1000 FPM or less for quiet operation. For
other velocities, use the following multipliers to obtain the correct CFM: 500 FPM = 0.5, 750 FPM = 0.75, 1250 FPM = 1.25, 1500 FPM =
1.5
, 2000 FPM = 2.0, 2250 FPM = 2.25.
2.) Bypass Dampers should be selected for 60% to 70% of the HVAC units rated CFM capacity. Recommended Bypass Damper velocity
is 1750 - 2250 FPM.

Dimensional Data

Typical Installation