Section 4

Auto-Zone Plus

4-32

Start-Up and Troubleshooting

2.3 Troubleshooting

2.3.1

Checking the Zone Manager Analog Inputs

Diagram

Overview

The analog input wiring can be checked at the
Zone Manager by checking voltages on the
Analog Input Connector.

If any of the RAT, SAT, OAT inputs read
greater than 5.0 volts then it is OPEN (no
sensor is connected), an input that reads less
than 0.1 volts is SHORTED. Check for wiring
problems before proceeding.

The AUX1-3 inputs should read greater than
5.0 volts if the attached contact is OPEN and
less than 0.5 volts if the contact is CLOSED
(contacts CLOSE between the input and
GND).

Note: The Zone Manager must be powered

for these tests.

Measurements

Meter Acceptable

Range

Ignore readings for any connections which are not used in the equipment

+12

23.4 – 25.2 volts

SAT

1.1 volts (140

°F) - 3.6 volts (40°F)

Typical is 2.5 volts @ 77

°F

RAT

1.9 volts (100

°F) - 3.6 volts (40°F)

Typical is 2.5 volts @ 77

°F

OAT

1.9 volts (100

°F) - 4.6 volts (-10°F)

Typical is 2.5 volts @ 77

°F

AUX1

If the input is OPEN, the voltage will be greater than 5.0 volts

If the input is CLOSED, the voltage will be less than 0.5 volts

AUX2

see AUX1 above

AUX3

see AUX1 above