Minimum default maximum, Wetbulb setpoints – Auto-Zone Control Systems Auto-Zone Plus Systems Installation & Operation (Version 03A) User Manual

Page 141

Advertising
background image

Auto-Zone Plus

Section 3

Programming

3-55

Wetbulb Setpoints









WB Setpoints

Calibration Offset

Outdoor Air..: 77.1

Cal. Offset..: 0.0

The only setpoint available for this unit is the Calibration
Offset
for the Thermistor Outdoor Air Temperature Sensor. If
location or other factors are causing the Outdoor Air
Temperature reading to be incorrect, the user can adjust the
reading up or down with this offset. Line 2 shows the current
temperature when you first enter this screen but it is not
dynamically updated after the offset is changed. You will need
to exit this screen, then return to this screen to see the effect of
the entered offset.

Minimum Default Maximum

Cal. Offset

-100.0°F

0.0°F

100.0°F