Minimum default maximum, Setpoint screen #5, Setpoint screen #6 – Auto-Zone Control Systems Auto-Zone Plus Systems Installation & Operation (Version 03A) User Manual

Page 109: Setpoint screen #7

Advertising
background image

Auto-Zone Plus

Section 3

Programming

3-23

Setpoint Screen #5







Setpoint Screen #6









Setpoint Screen #7









SUPPLY AIR SETPOINTS

Cool SAT DB: 2°

Heat SAT DB: 2°

CoolStage Up: 3 Min

CoolStage Dn: 1 Min

Min Cool Run: 5 Min

Min Cool Off: 3 Min

HeatStage Up: 3 Min

HeatStage Dn: 1 Min

Min Heat Run: 5 Min

Min Heat Off: 3 Min

If you have configured your unit for DX cooling this screen
will appear. This is the deadband used for DX Cooling and
Heat Stages only, and is not used for modulating heating and
cooling. The deadband is the temperature differential above
or below the setpoint that will be used between stages of
cooling and heating when staging up or down.

Minimum Default Maximum

Cooling SAT DB

1

°F 2°F 10°F

Heating SAT DB

1

°F 2°F 10°F

If you have configured your unit for DX cooling this screen
will appear. This screen allows you to set the time delay used
between DX Cooling stages and also the minimum run time
and minimum off time for the compressors.

Minimum Default Maximum

CoolStage Up

1 Min

3 Min

15 Min

CoolStage Dn

1 Min

1 Min

15 Min

Min Cool Run

1 Min

5 Min

15 Min

Min Cool Off

1 Min

3 Min

15 Min

If you have configured your unit for Staged Heating this
screen will appear. This screen allows you to set the time
delay used between Heating stages and also the minimum
run time and minimum off time for the heating device.

Minimum Default Maximum

HeatStage Up

1 Min

3 Min

15 Min

HeatStage Dn

1 Min

1 Min

15 Min

Min Heat Run

1 Min

5 Min

15 Min

Min Heat Off

1 Min

3 Min

15 Min