Setpoint screen #8 – Auto-Zone Control Systems Auto-Zone Plus Systems Installation & Operation (Version 03A) User Manual

Page 122

Advertising
background image

Section 3

Auto-Zone Plus

3-36

Programming

Setpoint Screen #8




Note: The Thermister Type III Sensors have a 0.4 degree accuracy.

TIP: This Calibration Offset is also useful as a troubleshooting tool. If you need to

simulate a heating or cooling mode, you can raise or lower the current zone
temperature far enough to put the zone into the desired mode.

Caution: The normal calibration offset should be a fairly small value. If you need

several degrees of offset, there might be a sensor problem or a location
problem.

















PD ZONE ADDRESS 1

Sensor Calibration

Rdg Offset

Zone: 75.4 0.0

If you have a more accurate digital thermometer that doesn't
agree with the current Zone Temperature reading, you can
adjust or calibrate the zone temperature reading.

Enter a positive number if the current reading is too low.

Enter a negative number if the current reading is too high.

Advertising