4 checking the zone manager network loop, Diagram meter set to read dc volts, Overview – Auto-Zone Control Systems Auto-Zone Plus Systems Installation & Operation (Version 03A) User Manual

Page 163: Measurements, Action

Advertising
background image

Auto-Zone Plus

Section 4

Start-Up and Troubleshooting

4-13

1.3.4

Checking the Zone Manager Network Loop

Diagram

Meter Set To Read DC Volts

TO

OTHER

ZONE

MANAGERS

TO

ZONE CONTROLLERS

and

CONSTANT VOLUME

UNITS IF USED

NETWORK LOOP

FROM THE COMMLINK OR

PREVIOUS ZONE MANAGER

T

R

SHLD

+

-

+

-

+2.0 VDC

to

+4.0 VDC

T - to - G

T

R

SHLD

+

-

+

-

+2.0 VDC

to

+4.0 VDC

R - to - G

The indicated readings are typical of a normally operating system. Actual readings may
vary slightly due to the number of units installed and other factors. Any significant
deviation from these values generally indicates a problem.

Note: These tests assume that the CommLink IV is connected and powered, and that all

Zone Managers which are connected are also powered.

Overview

Proper loop voltages are essential for reliable communications. It is normal to see
fluctuations on an operating communications loop. The average value should be close to the
acceptable range described below. Values will vary upon initial powerup for about 15-30
seconds as normal communications occur
.

Measurements

LOCAL LOOP

Acceptable Range

T - G (SHLD)

2.0 - 4.0 Volts DC

R - G (SHLD)

2.0 - 4.0 Volts DC

Action

Condition Action

Readings near Zero Volts

Check for shorted wiring.

If voltages are too high or too low on either
side

1. One or more devices connected to this

loop may have damaged comm driver
chips.

2. Wiring errors. Check for multiple loops

inadvertently “cross connected”, short
circuits, etc.

Advertising