Auto-Zone Control Systems Auto-Zone Plus Systems Installation & Operation (Version 03A) User Manual

Page 172

Advertising
background image

Section 4

Auto-Zone Plus

4-22

Start-Up and Troubleshooting

1.3.12 Troubleshooting

Checklist

No Zones are Communicating

• Is the CommLink IV connected and plugged in?

• Are the Zone Manager addresses set to 17?

In an Auto-Zone Plus system all Zone Managers are set to Address = 17.

• Are Comm Loop voltages correct? See the Comm Loop troubleshooting guides.

• Is the Comm Loop open or shorted?

• Are the Zone Controller address switches set correctly? See the addressing chart.

• Are the Zone Controllers powered? Check 24 VAC to the controllers.

• Is the Network Loop shorted to or connected to any of the Local loops? Check

Network Loop voltages.

• Is the System Manager connected to a Local loop?

Do not connect the system manager to the network loop!

Some Zones are communicating but others are not:

• Is the Zone Manager set for the correct number of zones?

• Are the Zone Controller address switches set correctly? See the addressing chart.

• Are the Zone Controllers powered? Check 24 VAC to the controllers.

• Is the REC LED on the missing Zone Controller “flickering”? See Zone Controller

introduction for location of the REC LED.

• Is the SCAN LED blinking an error code? See the Blink Code chart.

• Are Comm Loop voltages correct at the missing unit? See the Comm Loop

troubleshooting guide.

Advertising