Cv-c expansion board wiring, Warning, Figure 2-24: cv-c expansion board wiring – Auto-Zone Control Systems Auto-Zone Plus Systems Installation & Operation (Version 03A) User Manual

Page 67

Advertising
background image

Auto-Zone Plus

Section

2

Design Guide

2-35

CV-C Expansion Board Wiring


Notes:

Required VA For Transformer

Each CV-C Controller = 20VA Min.

Required VA For Transformer

Relay Expansion Board = 20VA Max.

24VAC

24VAC

GND

GND

Caution!

Relay Expansion Board Must Have Address Switches Set As

Shown Or The Board Will Not Function.

Caution:

Disconnect The Modular Cable Between The CV-C Controller And The

Relay Expansion Board Before Removing Power From The Relay

Expansion Board. Reconnect Power And Then Reconnect The Modular

Cable Between The CV-C Controller And The Relay Expansion Board.

1.)24 VAC Must Be Connected So

That All Ground Wires Remain

Common.

2.)All Wiring To Be In Accordance

With Local And National Electrical

Codes And Specifications.

Note:

Set-up, Programming And Monitoring Of The CV-C Controller Requires The

Use Of A Personal Computer And Prism Software.

EXPANSION

SENSOR

PRESSURE

T'STAT

24VAC

GND

Relay Outputs R6 Thru R13 May Be User

Configured For The Following:

0 - Not Used (Nothing connected to this

output )

1 - Heating Stage

2 - Cooling Stage

3 - Humidifier Enable

4 - Reheat Enable

5 - Scheduled Relay from Internal Schedule

6 - Scheduled Relay from External Schedule

(Only 1 Available!)

CV- C Controller

Relay Expansion Board

EXPANSION PORT

24VAC

IN

OUT

COM

Connect Expansion Board

to CV-C Controller

with Modular Cable

Not Used

PO
W

E

R

U4

U5

U3

U1

RELAY 1

RELAY 2

RELAY 3

ADDRESS

RELAY 4

RELAY 5

RELAY 6

RELAY 7

RELAY 8

N.

O

. C

O

NT
A

C

T

S

1 -
8

RE
LA

Y

CO

M

M

O

N

S

9,

10

Warning:

If One Transformer Is Used To Power The CV-C Controller And The

Relay Expansion Board, Polarity Must Be Strictly Observed. If The

Polarity Is Reversed, Serious Damage To Both Boards Will Result.

Figure 2-24:

CV-C Expansion Board Wiring

Warning:

Polarity is very important when connecting power to the controllers!
The grounded side of the control transformer must be connected to the
terminal labeled GND on the CV-C Controller. If a single transformer
is used to power more than one CV-C Controller you must connect
GND-to-GND and 24VAC-to-24VAC on each CV controller. Failure
to observe polarity will result in damage to one or more components
in your system.