0 setup – Magnum Energy ME-ARC Remote User Manual

Page 17

Advertising
background image

© 2012 Magnum Energy, Inc.

11

3.0 Setup

Table 3-1, ME-ARC Compatibility Matrix (cont.)

Button

FEATURES/SETTINGS

Model/

Level

Required

Default

Setting

Main

Menu

Menu

Heading/Item

Selections/

A d j u s t m e n t s

Range

METER

03

AGS

Meters

03A AGS Status

Read only display

≥Level 1

Read Only

03B DC Volts-AGS

03C Gen Run Time

03D AGS Temp

03E Since GenRun

04

BMK

Meters

04A BMK Status

Read only display

≥Level 1

Read Only

04B SOC

04C DC Volts-BMK

04D DC Amps-BMK

04E AH in/Out

04F Reset AH Out

04G Total AH Out

04H Minimum

VDC

04I Maximum VDC

SETUP

01 Re-

mote

Setup

01A Set Clock

Time= 12:00A-

12:00P

≥Level 1

12:00A**

01B Contrast

0-100%

100%**

01C Backlight

0-100%

50%**

01D Power Save

OFF, 1-60 Minutes

15 Minute

01E Temp Display

Fahrenheit, Celsius

Fahrenheit

02

Invert

Setup

02A Search Watts

OFF, 5-50 Watts

(1-Watt increments)

≥Level 1

5 Watts

02B LBCO

Setting

9.0-12.2*VDC

≥Level 2

10.0 VDC

02C AC In - Time

Connect Time=

12:00A-12:00P

≥Level 3

[1]

6:00A

6:00P

Disconnect Time=

12:00A-12:00P

02D AC In - VDC

Connect Volts=

9.0-15.9*(12V)

≥Level 3

[1]

11.0

Disconnect Volts=

9.0-15.9*(12V)

14.1

Advertising