0 operation – Magnum Energy ME-ARC Remote User Manual

Page 66

Advertising
background image

60

© 2012 Magnum Energy, Inc.

5.0 Operation

• Stack

Mode

A problem with the “other” stacked inverter has been

detected. Check that unit for a fault condition.

Remedy: This fault will automatically clear when the fault with the

other inverter is corrected.

• StackPhase

Either: 1. The AC input wiring is incorrect; 2. One phase

was lost from the AC input source; 3. One of the inverter’s internal transfer

relays is bad; or, 4. The inverter’s AC input circuit breaker may be open.

Remedy: If this fault doesn’t clear after checking these four recom-

mendations, perform an inverter reset (see Section 6.2).

5.3.4.3 Internal Fault Messages

The inverter continually monitors several internal components. If a condition

inside the inverter occurs that does not allow proper operation, one of the

following internal fault messages displays and the inverter shuts down to

help protect itself.

Remedy: If one of the following internal faults occurs, the inverter

will require an inverter or power reset to clear the fault. See Section

6 to perform an inverter or power reset. After resetting the inverter,

press the ON/OFF INVERTER pushbutton on the remote to turn the

inverter on and verify the fault has cleared (i.e. manual restart). If

the internal fault remains or returns, the inverter will require repair

at an Magnum Energy Authorized Service Center, for locations see

http://www.magnumenergy.com/Service/ServiceCenters-US.htm

.

• Internal

Bridge – This fault message displays when the FET bridge shuts

down after the inverter has been inverting—the inverter output circuit can no

longer detect any AC output voltage or current.
• Internal

Charger – This fault message displays when the FET bridge

shuts down because the charger circuit is trying to provide maximum current,

but is not detecting any current or voltage rise to the battery bank.
• Internal

NTC – This fault message displays when the internal NTC

(Negative Temperature Coeffi cient) temperature sensor suddenly causes a

very large but unexpected temperature change.
• Internal

Relay – This fault message displays when the internal AC

transfer relay is not closed while charging.