7.0 Using an AGS Module

66

© 2012 Magnum Energy, Inc.

SETUP: 04A Gen Run VDC Menu
This menu starts/stops the generator based on the battery voltage as shown

on the METER button’s 03B DC Volts-AGS menu. This menu provides the op-

tion to start the generator when the battery voltage gets low, and to stop the

generator once the battery reaches a higher voltage level, or has been fully

charged and goes into the Float Charge stage. Using voltage to automatically

start and stop the generator is a common method because it is considered

the simplest and easiest to understand. The 04A Gen Run VDC menu also

has a delay setting to minimize nuisance starts/stops and the short cycle run

times of the generator.
• Set Start Gen Volts – This setting will start the generator when the

battery voltage (on Terminals #3 & #4) decreases to or below this set-

ting continuously for the duration of the Set Start Volts Delay setting.
Default setting: Set Start Gen Volts = 11.5 VDC (12v), 23.0 VDC

(24v), 46.0 VDC (48v)
Range: OFF, 9.0-15.9 VDC (12v), 18.0-31.8 VDC (24v), 36.0-63.6 VDC (48v)

Where should I set Start Volts? When setting the VDC start voltage, it

must be high enough to not over-discharge the battery, but also low enough

to keep from nuisance starting the generator. Typically, start volts is set

based on what is determined to be approximately 50% of the battery ca-

pacity. Since this is an inverter/battery system, and the battery is normally

loaded, the VDC used to determine 50% battery capacity should be set lower

than what is shown on typical battery voltage SOC charts (approximately

11-11.5 in a 12-volt system), which show the battery at rest (not loaded).

Info: The DC voltage the AGS uses to determine when to autostart is

displayed in the AGS: 08 AGS TECH menu under the AGS VDC meter.

Example: Using a 12-volt battery as an example, a typical SOC (State of

Charge) battery chart will show that 12.2 VDC is considered 50% SOC. This

voltage is a battery “at rest,” meaning it has no load connected and has been

at rest for a minimum of 30 min. While this voltage is accurate under these

at rest conditions, this same voltage with a load applied means the battery is

well above 50% SOC, and should be set much lower. The larger the battery

bank the less the voltage will be affected by a load applied to the battery

bank. A typical start voltage setting would be between 11.0 VDC - 11.5 VDC

for a 12-volt system.
• Set Start Volts Delay This setting determines how long the Start

Gen Volts parameter must be continuously maintained before the gen-

erator autostarts. This ensures the generator does not nuisance start.

By setting a delay, momentary surge loads will not start the generator

when the battery voltage dips due to the heavy load applied to the

battery.
Default setting: Set Start Volts Delay = 120 Seconds
Range: 0-127 Seconds, 1-127 Minutes

Where should I set Start Volts Delay? Determine what loads will be

running when the generator needs to start. The larger the load the shorter

the delay time setting. When a large load is applied to the battery bank the

battery voltage drops quickly, so the delay time should be short to ensure

the batteries are not over-discharged. If you are unsure what loads might be

running or where to set the start delay, error on setting a shorter time such

as the default of two minutes (to protect batteries from over-discharge).