Setup: 04i gen warm-up time menu, Setup: 04j gen cooldown time, 2 me-ags-n functional tests – Magnum Energy ME-ARC Remote User Manual

Page 82: 0 using an ags module

Advertising
background image

7.0 Using an AGS Module

76

© 2012 Magnum Energy, Inc.

SETUP: 04I Gen Warm-up Time Menu
This menu allows the generator to run (i.e., warm up) before it connects to

the inverter/charger, or powers the battery charger and any pass-thru loads.

Most generators need to warm up before a load is supplied.

Set Gen Warm-up Time This setting is the amount of time the gen-

erator is allowed to warm up before connecting to the inverter/charger.
Default setting: Set Gen Warm-up Time = 60 sec.
Range: 0-127 Seconds, 1-127 Minutes

Where should I set Gen Warm-up Time?

Check with your generator

manufacturer. Typically, smaller generators (~2-3KW) need at least 60 seconds

before applying a load; larger generators require a longer warm-up time.
SETUP: 04J Gen Cooldown Time
This menu allows the generator to continue to run after it disconnects from

the inverter/charger and prior to autostopping (i.e., cooldown). Allowing

the generator to cool down after the load is disconnected helps to prolong

generator engine life.

Set Gen Cooldown Time This setting is the amount of time the genera-

tor is allowed to cool down after it disconnects from the inverter/charger.
Default setting: Set Gen Cooldown Time = 60 sec.
Range: 0-127 Seconds, 1-127 Minutes

Where should I set Gen Cooldown Time? Check with your generator

manufacturer. Most generators need at least 60 seconds to cool down after

being disconnected from a load.

Info: The warm-up and cooldown features prevent the generator

from connecting to the inverter’s AC input. Since the inverter has

only a single-source input, it cannot distinguish between grid or

generator input. So, during warm-up or cooldown, the inverter will

prevent any AC input from connecting. When either warm-up or

cooldown is activated, it will disconnect any AC source connected

to the inverter’s AC input (i.e., grid or generator) until the time

period (warm-up or cooldown) is over.

7.2 ME-AGS-N Functional Tests

Once you have used the ME-ARC to establish all the autostart/autostop set-

tings you need, perform the following tests to verify that the AGS system is

functioning correctly and there is communication between the remote/inverter

and the ME-AGS-N.

7.2.1 Remote to Generator Communication Test

This section describes using the ME-ARC remote to start the generator and

to determine the current AGS status.

7.2.1.1 Determining AGS Status

Use your remote control to determine the AGS’s status by pressing the METER

button until the bottom line displays “01 DC Meters”, rotate the SELECT knob

to the 03 AGS Meters menu, and then press the SELECT knob (top line shows

03A AGS Status and the bottom line displays the current status of the AGS,

i.e., Ready). An AGS status of Off or Ready indicates the remote/inverter is

correctly communicating with the AGS. If the AGS status displayed is not Off or

Ready, then refer to

Section 7.8.2

“Resolving Operational Statuses” or

Section

7.8.3

“ME-AGS-N Faults using your Remote” for assistance before continuing.

Advertising