29

3.0 Setup

begins to operate in parallel with the incoming utility power to support

the inverter loads (i.e., Load Support Mode

¹

). Typically, set to the size

of the AC circuit breaker that feeds the AC1 input.

Default setting: 30 Amps
Range: 5-60 Amps
Set AC2 Input Amps – This setting determines the AC amps level at

which the MSH4024RE inverter/charger begins to back off the battery

charger to reduce the load on the incoming generator power (that is

connected to the AC2 input) in order to continue powering the inverter

loads. This setting also determines when the MSH4024RE begins to

operate in parallel with the incoming generator power to support the

inverter loads (i.e., Load Support Mode¹). Typically, this is set to the size

of the generator’s circuit breaker that feeds the inverter AC2 input, or to

the maximum output amperage ability of the generator.
Default setting: 20 Amps
Range: 5-60 Amps

Where should I set AC Input Amps? This setting controls the input current

differently depending on the inverter/charger model and the AC input wiring

confi guration. Set as described below for your particular model:

ME, MS, and RD Series: These models have two inputs (HOT IN 1 and HOT

IN 2), but the current is only monitored on HOT IN 1. On these models—

when wired as a dual-in confi guration or as a single-in confi guration with

only the HOT IN 1 connected—the AC Input Amps setting should be set to

the size of the AC circuit breaker that feeds the HOT IN 1 input. On these

models, when wired as a single-in confi guration with HOT IN 1 and HOT IN

2 jumped together, set the AC Input Amps setting to half (x½) the input

breaker size—as ½ the current will pass through HOT IN 1 and the other

½ through HOT IN 2 simultaneously.
MS-AE and MS-PAE Series: These models have two inputs (HOT IN 1

and HOT IN 2), with the current monitored on each input at the same

time. On these models, since the input is from a single AC source, both of

the input currents are added together and divided in half to determine the

AC Input Amps setting. Whether the input circuit breaker is a dual-pole

(120/240 VAC input) or a single-pole (120 VAC only), set the AC Input

Amps setting to the value of only one of the breaker poles (i.e. 30A dual-

pole = 30A setting, 30A single-pole = 30A setting).
MS-E, MS-PE, MSH-RE and MSH-M Series: These models may have

one (AC1) or two (AC2) inputs, with the current monitored on each input

separately. On these models, set the AC Input Amps setting to match the

input AC circuit breaker size.
MM, MM-AE and MMS Series (and any export version of these

models): These models do not monitor current on the input, therefore

cannot benefi t from the AC Input Amps setting or feature. On these

models, the AC Input Amps setting may be displayed and allow selection/

adjustment, but will not do anything to reduce the battery charger current.

Note¹: The MS Hybrid (MSH) Series inverter/chargers have Load Support

Mode, which allows the inverter power to operate in parallel with the incoming

AC power (Grid or Gen). This feature uses additional power from the inverter’s

battery to run loads greater than what the incoming AC power can run alone,

and prioritizes the power of any external DC source (i.e., solar, wind, etc.)

over the incoming AC power to run inverter loads. For more information, see

the Load Support Mode section in the MSH Owner’s Manual.