3.0 Setup

• 02F Power Up Always – Allows the inverter to power up and provide

AC power automatically once DC voltage is connected to the inverter.
Default setting: OFF
Range: OFF, ON

What is the Power Up Always feature? Normally, when DC power is con-

nected to the inverter, the user is required to press the power button—on the

inverter or remote—to turn the inverter on. When the Power Up Always feature

is activated by selecting “ON”, the inverter is automatically turned on and

starts searching or inverting—depending on the SETUP:02 Invert Setup/02A

Search Watts setting. Once the inverter has connected to DC power and is

automatically turned on, the power button—on the inverter or remote—can

be used to turn the inverter on or off.
Why use the Power Up Always feature? Some customers are familiar with

Uninterruptable Power Supplies (UPS) that power-up automatically when DC

power is connected. The Power Up Always feature can be used by customers

that want to obtain the same automatic power-up feature with which they

are familiar.

SETUP: 03 Charger Setup

03A AC Input Amps – This selection ensures that the combined current

draw from the charger and the AC loads does not exceed the maximum

input current that is available from the incoming AC power. Whenever the

utility or generator is connected to the inverter’s input, the current used

to power the AC loads and to charge the batteries is monitored. When the

total current used to power the AC loads and charge the batteries begins

to approach the AC Input Amps setting, the current used for charging the

batteries is automatically reduced. This ensures the AC loads have all the

available current from the incoming AC power when needed.

Setting for all models except MSH4024RE:

Set AC Input Amps – This setting determines the level in AC amps

at which the inverter/charger begins to back off the battery charger to

reduce the load on the incoming utility/generator power and continue

powering the inverter loads.
Default setting: 30 Amps
Ranges: 5-60 Amps

Settings for MSH4024RE:

Info: The MSH4024RE inverter/charger has two independent AC

source inputs (AC1/GRID, AC2/GEN) with independent AC input

amps settings for each. The Set AC1 Input Amps and Set AC2 Input

Amps menus only display if the remote is connected to a dual input

source inverter/charger.

Set AC1 Input Amps – This setting determines the level in AC amps

at which the MSH4024RE inverter/charger begins to back off the battery

charger to reduce the load on the incoming utility/grid power (that is

connected to the AC1 input) and continue powering the inverter loads.

This setting also determines when the MSH4024RE inverter/charger

Advertising