4.0 Menu Map

SETUP

Status/Fault

02 Invert Setup

continued….

02D AC In - VDC

11.0 to 14.1 VDC

Defaults: 11.0/14.1 VDC

(12V)

, 22.0/28.2 VDC

(24V)

,

44.0/56.4 VDC

(48V)

Set Connect

Volts= 9.0

Set Connect

Volts= 11.0

S

Set Disconnect

Volts= 9.0

Set Disconnect

Volts= 14.1

Ranges: 9-16

(12V)

, 18-32

(24V)

, 36-64

(48V)

SETUP button menu map continues on next page

Status/Fault

03 Charger Setup

03A AC Input

Amps = 30A / 20A

Ranges: 5-60A

Defaults: AC1=30A, AC2=20A

S

02E AC In - SOC

50% to 100% SOC

02F Power Up

Always OFF

Set Connect

SOC = 20%

Set Disconnect

SOC = 21%

S

S

S

Set Power Up

Always = OFF

S

Set Connect

SOC = 50%

Set Connect

SOC = 98%

Set Disconnect

SOC = 100%

Set Power Up

Always = ON

Defaults: 50% (Connect), 100% (Disconnect)

Ranges: 20-98% (Connect), 21-100% (Disconnect)

Default: OFF

Range: OFF, ON

03B Battery Type

Flooded

Range: GEL, Flooded, AGM1, AGM2, Custom

Default: Flooded

Set Absorb

Volts= 14.4

Set Float

Volts= 13.2

Set EQ

Volts= 15.5

Set Battery Type

Flooded

Set Battery Type

Custom

Ranges (Custom): 12-16 VDC

(12V)

,

24-32 VDC

(24V)

, 48–64 VDC

(48V)

Set Battery Type

GEL

S

S

S

S

03C Max Charge

Rate = 100%

Set Max Charge

Rate = 0%

Set Max Charge

Rate = 10%

Set Max Charge

Rate = 100%

Range: 0-100%

Default: 100%

S

Set AC1 Input

Amps = 5A

Set AC1 Input

Amps = 30A

Set AC1 Input

Amps = 60A

S

Set AC2 Input

Amps = 5A

Set AC2 Input

Amps = 20A

Set AC2 Input

Amps = 60A

S

Set Connect

Volts= 16.0

Set Disconnect

Volts= 16.0

*

* AC2 only displays on MSH4024RE models.

Figure 4-3, SETUP Button Menu Map