0 using an ags module – Magnum Energy ME-ARC Remote User Manual

Page 73

Advertising
background image

© 2012 Magnum Energy, Inc.

67

7.0 Using an AGS Module

• Set Stop Gen Volts – This setting will stop the generator when the

battery voltage (on Terminals #3 & #4) increases to or above this set-

ting continuously for the duration of the Set Stop Volts Delay setting. To

allow the battery bank to go through a full bulk and absorption charge,

this setting should be set to Float.

Default setting: Set Stop Gen Volts = 14.4 VDC (12v), 28.8 VDC

(24v), 57.6 VDC (48v)
Range: OFF, 9.1-16.0 VDC (12v), 18.2-32.0 VDC (24v), 36.4-64.0 VDC

(48v), Float

Where should I set Stop Gen Volts? Typically, when using a generator

to charge batteries, most individuals only charge the batteries to 80-85%

to compromise between minimizing fuel usage and maximizing battery life.

This is done by having the generator start on low battery voltage, and then

stop at a higher voltage (i.e., the Stop Gen Volts setting). When deciding

where to set the Stop Gen Volts setting, it must be lower than the invert-

er’s Absorb Voltage setting (determined by the SETUP: 03B Battery Type

menu). Otherwise, the charger will enter Absorption Charge mode—which is

required to maintain the batteries at a constant voltage level—and the bat-

tery voltage will not reach the Stop Gen Volts setting, which will cause the

generator to run until it is out of fuel or until it reaches the SETUP: 04F Max

Gen Run Time setting.
Therefore, after reading this some will think that they should just set the

Stop Gen Volts setting slightly lower than the absorption level to ensure

the charger always reaches the Stop Gen Volts setting before it goes into

the Absorption Charge mode. However, temperature changes can affect the

absorb voltage setting¹ and may require you to readjust the Stop Gen Volts

setting seasonally. If you are in a normally cold climate (<32°F), the actual

absorb charge voltage will increase. So, the Stop Gen Volts setting should be

set well above the absorb voltage setting (~.5V above for 12-volt systems).

If you are normally in a hot climate (>95°F), the actual absorb charge volt-

age will decrease. In that case, the Stop Gen Volts setting should be set well

below the absorb voltage setting (~.5V below for 12-volt systems).
A simpler way to charge the batteries to 80-85% and to automatically allow

a temperature-compensated charge to the batteries (no seasonal adjust-

ment required) is accomplished using the settings below:
• Set

the

Stop Gen Volts setting to Float

• Set

the

Absorb Voltage setting (SETUP: 03B Battery Type) to the volt-

age level at which you want the generator to turn off (normally ~ 14.5

volts for fl ooded batteries in a 12-volt system)

• Set

the

Absorb Done Time setting (SETUP: 03E Absorb Done Time) to

0.1 hours (lowest setting)

Using these settings, when the batteries reach a low voltage level the gen-

erator turns on (per the Set Start Gen Volts setting) and charges the battery

to the temperature-compensated Absorb Voltage setting. After reaching the

absorption voltage level, the inverter/charger goes into Absorption Charge

mode and is there for only six minutes (0.1 hours) before it goes to Float

Charge mode. Once the inverter/charger enters Float Charge mode, the AGS

will autostop the generator.

Note¹: When the inverter’s Battery Temperature Sensor (BTS) is connected,

the actual absorb charge voltage will increase or decrease to ensure correct

charging as the battery temperature changes.

Advertising