7.0 Using an AGS Module

7.0 Using a ME-AGS-N Module

The AGS menus under the CTRL, METER, SETUP, and TECH buttons on the

ME-ARC remote allow you to customize and monitor operating parameters,

and to help troubleshoot your autostart/autostop generator system. Use the

mini-index below to direct you to the appropriate section.
7.1 AGS Setup

p. 65

7.4 Enabling the AGS

p. 81

7.2 AGS Functional Tests

p. 76

7.5 Start/Stop Gen

p. 81

7.3 AGS Operation/Monitoring

p. 77

7.6 AGS Menu Maps

p. 83

7.1 ME-AGS-N Setup

Press the SETUP button on the ME-ARC remote, and then rotate the SELECT

knob to the 04 AGS Setup display. The menus available from this screen al-

low the generator to be automatically started and stopped based on many

different conditions. From Table 7-1, determine the specifi c autostart and

autostop conditions with which you want the generator to be automatically

controlled, and then use that specifi c menu setting to confi gure the AGS.

Info: For information on using the CTRL, METER, and TECH but-

ton menus, refer to Section 7.3 “ME-AGS-N Operation/Monitoring”.

Note¹: Only applicable to MS-PAE, MS-PE and MSH inverters.

Note²: Autostart/stop conditions using SOC require the ME-BMK.

Autostart Condition Autostop Condition

SETUP Menu Page

Starts on low battery

voltage (DC voltage

connected to Termi-

nals #3 and #4)

Stops on higher battery

voltage

04A Gen Run

VDC

66

Stops at Float charge

after a set time period

(using Absorb Done Time

setting)

04A Gen Run

VDC (Set Stop

Gen Volts =

Float)

66

Stops at Float charge

after battery current

requirement is low (using

Absorb Done Amps)

04A Gen Run

VDC (Set Stop

Gen Volts =

Float)

66

Stops at Float charge us-

ing a battery SOC setting

(using Absorb Done SOC

setting)²

04A Gen Run

VDC (Set Stop

Gen Volts =

Float)

66

Starts at a set time

daily

Stops at a different set

time daily

04B Gen Run

Time

68

Starts on high AC

amps to an inverter

load¹

Stops on lower AC amps

to an inverter load¹

04C Gen Run

Amps

68

Starts when the bat-

tery SOC² is low

Stops when the battery

SOC² is higher

04D Gen Run

SOC

69

Starts when tempera-

ture increases

Stops after a set time

period

04E Gen Run

Temp

70

Table 7-1, ME-ARC Autostart/Autostop Matrix