6.0 Troubleshooting

6.2 Performing an Inverter Reset

To perform an inverter reset (also known as a soft reset), press and hold the

Power ON/OFF button (see Figure 6-1) for approximately fi fteen (15) seconds

until the Charging/Inverting Status LED comes on and fl ashes rapidly. Once

the rapid fl ashing has begun, release the Power ON/OFF button. The Status

LED will go off after the button is released.
After the inverter reset is completed, press the Power ON/OFF button to turn

the inverter ON.
Some older inverter models do not allow an inverter reset. If the inverter reset

fails, you will need to perform a power reset using the procedure below. In

either case, if an internal fault does not clear the inverter will require repair

at a Magnum Authorized Service Center (ASC).

Info: The Power ON/OFF button is a small momentary type switch

which operates by lightly pressing and releasing.

Info: All adjustable inverter/charger settings in the ME-ARC (except

for the SETUP menu’s 01B Contrast, 01C Backlight, and the CTRL

menu’s 03 Gen Control—which revert back to default) are saved in

non-volatile memory and are preserved until changed. This occurs

even if an inverter reset is performed, or if all power to the remote

or inverter is removed.

Figure 6-1, Performing an Inverter Reset

1. Press and hold the Power ON/

OFF pushbutton for 15 seconds.

2. Watch the Charging/Inverting

Status LED, after approximately

15 seconds it should come on and

flash rapidly (almost a flutter) to

indicate the inverter has reset.

The Status LED will go off after

the pushbutton is released.

6.3 Performing a Power Reset

To perform a power reset (also known as a hard reset):

1. Remove all AC power (utility or generator power) to the inverter.
2. Open all the inverter DC disconnects (or disconnect the positive bat-

tery cable to the inverter).

3. Ensure the inverter(s) and the remote are disconnected from all AC

and DC power (the remote display will be blank).

4. After the inverter(s) has been disconnected from all power for 30

seconds, reconnect the inverter DC disconnects (or reconnect the

positive battery cable) and resume operation.

Info: If DC disconnects are not used, there may be a momentary

spark when the positive battery cable is connected to the inverter’s

terminal. This is normal and indicates that the inverter’s internal

capacitors are being charged.