© 2012 Magnum Energy, Inc.

71

7.0 Using an AGS Module

Info: If the temperature start feature is not needed, ensure this

setting is set to the OFF position.

• Set Gen Run Temp Time – This menu sets the amount of time the

generator runs after a temperature autostart.
Default setting: Set Gen Run Temp Time = 2.0 Hrs
Range: 0.5-25.5 Hrs

When the temperature around the remote temp sensor (per the METER: 03D

AGS Temp display) increases to the Gen Run Temp Start setting, the genera-

tor immediately starts and runs based on the Gen Run Temp Time setting.

When this run time period is fi nished, the temp sensor reading is checked.

If the temperature sensor (or thermostat control if using the optional pigtail

adapter) reading is below the Gen Run Temp Start setting, the generator

will autostop. If the temperature sensor (or thermostat control) reading is

above the Gen Run Temp Start setting, the generator will continue to run for

a second run time period. At the end of this second run time period, the tem-

perature sensor reading (or thermostat control) is checked again. This cycle

continues as long as the CTRL: 03 Gen Control menu is set to AUTO, or the

SETUP: 04F Max Gen Run Time setting is reached, whichever occurs fi rst.
Why should I use Gen Run Temp? Typically, in a mobile application such

as in an RV or on a boat where the air conditioning (A/C) unit is too much

power for the inverter to run from the batteries, this feature is used to start

a generator to run the A/C unit. Many RV and marine customers travel with

pets and they do not want to leave the pets inside on a hot day. With this

feature, you could set the A/C unit to turn on and leave. Whenever the inside

temperature rises to the start setting, the generator autostarts to provide

power to the A/C unit. This would keep the area cool and comfortable—plus,

while the generator is on, the inverter batteries are being charged.
Where should I set Gen Run Temp Start? If using this feature to power

an A/C unit, the Gen Run Temp Start setting should be slightly above the

temperature setting of the thermostat controlling the air conditioner unit.

Once the Gen Run Temp Start setting is reached, the gen starts providing

power to the A/C unit. The reason the Gen Run Temp Start is set above the

A/C unit’s thermostat setting is to ensure the A/C unit runs when the genera-

tor starts. If the Gen Run Temp Start setting is below that of the A/C unit’s

thermostat setting, the generator runs but the A/C unit is not calling for a

run period or cooling. In other words, your generator is running but the pow-

er is not being used by the A/C unit—resulting in wasted fuel and run time.

Info: If using the temperature autostart feature to start a genera-

tor that is powering two air conditioners, it is suggested that the

second air conditioner’s thermostat be set 2° to 5° higher than

the fi rst air conditioner. This staggered setting allows the fi rst air

conditioner to start and run in an effort to keep the coach cool. If

the temperature continues to rise inside the coach, the second air

conditioner turns on.

How long should I set the Gen Run Temp Time? When using the tem-

perature autostart feature, the generator autostarts and runs until the Gen

Run Temp Time setting or the SETUP: 04F Max Gen Run Time setting is

reached, whichever occurs fi rst. This means you could set the time to the

lowest time setting (0.5 Hrs), knowing the generator will attempt to run until

the temperature setting is met.