7 me-ags-n remote status messages, 0 using an ags module – Magnum Energy ME-ARC Remote User Manual

Page 92

Advertising
background image

7.0 Using an AGS Module

86

© 2012 Magnum Energy, Inc.

7.7 ME-AGS-N Remote Status Messages

A status message may be an operational or fault message. Access the AGS

status menu (METER button’s 03A AGS Status menu) to view the AGS’s cur-

rent operating status. This menu is important when determining if the AGS

is working correctly, or for troubleshooting an AGS installation.

7.7.1 AGS Remote Operational Statuses

Refer to Table 7-2 below for a brief description of the possible AGS opera-

tional statuses that may display (depending on your remote).

STATUS

DESCRIPTION

AC In

The inverter/charger is connected to another source

such as a grid or an alternate generator, and is not

controlled by the AGS. When AC In displays, the AGS

is prevented or locked out from all autostarting condi-

tions, except for when the generator needs to exer-

cise—if enabled.

Gen Cooldown The autostop setting has been met in one of the gen-

erator autostart/autostop menus and the generator has

been disconnected from the inverter/charger. However,

the generator is still runs until the cooldown time is met

(as per the SETUP: 04J Gen Cooldown Time setting).

Gen Warm-up

The AGS is attempting to start the generator and a

time period has been set under the SETUP: 04I Gen

Warm-up Time setting. Once the AGS status indicates

Warm-up”, the inverter/charger’s AC input ignores any

incoming AC power. This prevents the inverter/charger

from loading the generator during warm-up. Once the

AGS has determined that the generator is running, the

warm-up time setting must be met before the genera-

tor can connect to the inverter/charger.

Manual Run

The generator was started manually from a start/stop

switch directly connected to the generator, or from the

CTRL: 03 Gen Control menu.

Note: The AGS determines that the generator has been manually turned

on by sensing a gen run sense voltage to Terminal #2 on the AGS’s 8-port

terminal block. However, if the Gen Type DIP switch is set to “2-Wire

Standby” (which doesn’t require a gen run sense voltage), manually turn-

ing the generator on displays a status of AC In rather than Manual Run.
No Comm

The AGS is not communicating with the inverter/re-

mote.
This is a normal status if there is no AGS-N (Network

version) connected in the system.
If an AGS is installed, then refer to Section 7.8.2 “Re-

solving Operational Statuses” for assistance.

Off

The CTRL: 03 Gen Control menu is set to OFF. This set-

ting will not allow the AGS to autostart the generator.

Table 7-2, AGS Remote Operational Statuses

Advertising