Setup: 04e gen run temp menu, 0 using an ags module – Magnum Energy ME-ARC Remote User Manual

Page 76

Advertising
background image

7.0 Using an AGS Module

70

© 2012 Magnum Energy, Inc.

The BMK already uses voltage, time, and current to determine the true SOC

of the batteries, so little guesswork is needed to determine the settings.
• Set Start Gen SOC – This menu is used to set the SOC level for auto-

starting the generator.
Default setting: Set Start Gen SOC = OFF
Range: OFF, 20-90%

• Set Stop Gen SOC – This menu is used to set the SOC level for

autostopping the generator.
Default setting: Set Stop Gen SOC = 90%
Range: 21-100%

Info: There is no start or stop delay time needed since the ME-BMK

already displays an accurate state of charge of the batteries.

Where should I set Gen Run SOC? Most battery manufacturers recom-

mend that for optimum life, deep-cycle batteries should not be discharged

below 50% SOC. The ME-BMK determines the battery’s SOC by using a DC

shunt to measure the fl ow of current in and out of the battery. The SOC

meter gives you an accurate reading of remaining capacity in the battery

bank. Set the Start Gen SOC level to 50%, or to 60% if you do not want to

discharge the batteries quite as much. When considering the Stop Gen SOC

setting, keep in mind that running the generator past 90% SOC delivers

very little current to get that last 10% into the batteries. Thus, it is common

to stop the generator at 90% to save fuel and run time on the generator.

However, if the SOC stop setting is less than 100%, the batteries should be

charged to 100% as often as possible (~ once a week, or every other dis-

charge cycle) in order to avoid sulfation of the battery plates.
SETUP: 04E Gen Run Temp Menu
This menu allows you to set and enable a temperature value that will auto-

matically start the generator—typically to power an air conditioner for cool-

ing—based on an increase in temp, or by using an A/C thermostat control.

Info: The optional ME-PT1 or ME-PT2 pigtail adapters can be used to

connect an A/C or relay control circuit. For more information, refer

to the instruction sheet for each pigtail adapter (part number 64-

0025 for ME-PT1 instructions, or 64-0026 for ME-PT2 instructions).
Info: This temperature autostart feature requires that the AGS’s

remote temp sensor cable or an optional ME-PT1 or ME-PT2 pigtail

adapter be connected to the AGS’s REMOTE port. When using the

remote temperature sensor, the location of the temperature sensor

determines the area being monitored for temperature.

• Set Gen Run Temp Start – This menu is used to enable and set the

temperature that triggers a generator autostart.
65F - 95F (18C - 35C) – These settings determine the rising tempera-

ture value that triggers a generator temperature autostart.
Ext Input – This setting is used when an optional pigtail adapter (ME-

PT1, or ME-PT2) is used. When an AGS pigtail adapter is connected to

the AGS’s REMOTE port, an external command—either from a thermo-

stat connection on an air conditioner control circuit or an external relay

control circuit—is recognized and causes the generator to start.
Default setting: Set Gen Run Temp Start = OFF
Range: OFF, Ext Input, 65-95F or 18-35C

Advertising