3.0 Setup

CTRL: 02 CHG (Charge) Control
02 CHG Control enables you to set the Charge mode to Multi-Stage, Force

Float, or to Restart Bulk. Most of the time the charger should be left in the

Multi-Stage setting, but to override this setting use the CTRL button and the

02 CHG Control menu. The charger can be forced into the Float mode or you

can start the Bulk mode using the Force Float or Restart Bulk settings from

the CTRL button’s 02 CHG Control menu.
• Multi-Stage

This charge profi le starts in Bulk mode (maximum cur-

rent). It transitions to the Absorption stage (constant voltage). When the

Absorption voltage is reached (as determined by the SETUP button’s 03E

Absorb Done menu), it transitions to the fi nal charge stage as selected

in the SETUP menu’s 03G Final Charge Stage menu item.

Info: Multi-Stage must be selected in order for the Final Charge

Stage setting to be used.

• Force

Float

This charge profi le forces the charger to stay in Float mode

as long as AC is present and the charger is active. Force Float is most

often used when another source of charging such as PV, wind, or hydro

is available to keep the batteries at or above the fl oat voltage. If AC is

disconnected and then reconnected, the charger will go directly to Float

mode and will not initiate a Bulk or Absorption charge cycle.

CAUTION: Using the Force Float setting may not fully charge the

batteries. Most batteries require a Bulk and Absorption charge cycle

in order to fully recombine the electrolyte in the batteries and bring

the specifi c gravity to the proper level. Be sure to check with your

battery manufacturer before using this setting.
Info: If Silent is selected from the SETUP menu’s 03G Final Charge

Stage menu item, you can override this selection with Force Float

to temporarily fl oat the batteries.

• Restart

Bulk

– This selection restarts the Bulk cycle from any stage in

the charge cycle. The Restart Bulk setting is useful when a full multi-

stage charge cycle does not bring the specifi c gravity of the batteries to

the proper level.

Info: The Restart Bulk setting automatically defaults back to the

Multi-Stage setting once the inverter/charger status displays “Bulk

Charging”.
Info: If you have to continually restart the bulk cycle in order

to bring the batteries to full charge, check the settings from the

SETUP button’s 03 Charger Setup menu to ensure the batteries

are fully charged at the end of a regular multi-stage charge cycle.

Check with the battery manufacturer for proper battery charger

settings.

CAUTION: Frequently restarting the Bulk cycle may result in over-

charging of the batteries.

CTRL: 03 Gen Control
03 Gen Control is used for controlling a standby generator that is connected

to the system and using the optional ME-AGS-N module. Once the AGS-N