4.0 Menu Map

TECH

continued….

Read Only display

04 Fault History

Press SELECT

03 Inv Model

MSH4024RE

Set SETUP

PIN = 0000

Set SETUP

Unlock SETUP

Set SETUP

Lock SETUP

06 Ext Control

###

07 Load Defaults

Press SELECT

07 Load Defaults

Defaults in #.#

07 Load Defaults

DEFAULTS LOADED

Factory Defaults

Loaded

06 Ext Control

Press SELECT

06 Ext Control

No Ext Control

05 SETUP PIN

SETUP Unlocked

Set SETUP

Change PIN

S

S

S

S

Read Only displays

S

Read Only display

04A Inv Faults

Press SELECT

Fault..

*

H1 FETs: ###F

Range: H1 to H9, Day since, Time, Status, VDC, ADC,

BTS Temp, Transformer Temp, Transistor (FETs) Temp

Fault..

*

H1

Status..

S

Fault..

*

H1 Tfmer: ###F

Fault..

*

H1 BTS: ###F

Fault..

*

H1 D- 0 HH:MM

Fault..

*

H1 VDC DCA

Refer to the AGS TECH menu maps (see Figure 7-3)

04B AGS Faults

Press SELECT

04C Clear Faults

Press SELECT

04C Clear Faults

HISTORY CLEARED

S

04C Clear Faults

Clearing in #.#

Press and hold SELECT

button for 5 seconds

LEGEND

Menu Selections

Menu Button

Default/Current

Setting

Change Settings

Menu Heading

Set Search Watts

5 Watts

SETUP

S

Press button

Press SELECT

02A Search Watts

5 Watts

*Specific fault is listed; if no fault,

“No Error Record” displays

= current setting*

* For this menu map, the arrow denotes the factory default setting

If “Yes”, only a 3-digit

number displays

Press and hold SELECT button

for 5 seconds

Figure 4-5, TECH Button Menu Map