5.0 Operation

LED

Status

Meaning

PWR

(green)

OFF

1. Inverter is disabled; 2. Remote’s in Power Save

mode – press any button to activate LEDs; 3. No

power to remote (check remote cable or power

to inverter); or, 4. No AC power at the inverter’s

AC output terminals.

ON

AC power is available from inverter, utility, or

generator at the inverter’s AC output terminals.

FAULT

(red)

OFF

Normal operation.

ON

A fault condition has been detected. Check the

LCD display to fi nd and correct the cause.

CHG

(green)

OFF

1. Remote is in Power Save mode – press any

button to activate LEDs; or, 2. Charger off – no

utility or AC generator present.

ON

Bulk, Absorb, Float, or Equalize charge mode

(see the LCD display to determine charge

status).

BLINKING,

display says

Charger

Standby

The charger is in Charger Standby mode. This

occurs when the ON/OFF CHARGER button is

pressed to disable the charger.

BLINKING,

display says

Full Charge

or “Silent

The charger is in Battery Saver mode. This mode

monitors battery voltage level and only charges

if the battery voltage decreases to a low level.

Silent mode will automatically start charging

when the ReBulk setting is reached.

BLINKING,

display shows

a charging

status (i.e.,

Bulk, Absorb,

Float)

The charger current is automatically decreased

because: 1. Charger Back-off – the inverter’s

internal temperature is getting hot, current is

decreased to reduce/maintain temperature; or, 2.

Low AC Input Voltage – the input AC voltage is

low, charger is disabled to help stabilize incoming

AC voltage to prevent AC disconnect.

BLINKING,

display does

not show any

charge status

The inverter is detecting AC voltage (from utility

or an AC generator) on the inverter’s AC input

terminals.

INV

(green)

OFF

1. Inverter is disabled; or, 2. Remote is in Power

Save mode - press any button to activate LEDs.

ON

Inverter is enabled – 1. Supplying AC power on

the output; or, 2. In Inverter Standby (if both

INV and CHG LEDs are on); the inverter will

automatically supply AC power to the loads if

utility or generator power is lost.

BLINKING

Inverter is in Search mode (the AC load is below

the SETUP menu’s 02A Search Watts setting).

5.3.5 LED Indicator Guide

Use the LEDs along with the LCD display to determine the operating status.

Table 5-1, LED Indicator Guide