7.0 Using an AGS Module

Note¹: Generator autostarting based on Quiet Time Topoff using battery

SOC (State of Charge) parameters requires the optional Battery Monitor Kit

(ME-BMK or ME-BMK-NS) to be installed and enabled.

Note²: This voltage is scaled depending on your battery system; ≤0.3 for

12-volt systems, ≤0.6 for 24-volt systems, and ≤1.2 for 48-volt systems.

Set Start Quiet Hour – Set the hour for Quiet Time to start.

Set Start Quiet Minute Set the minute for Quiet Time to start.

Set Start Quiet AM-PM Set AM or PM for the start of Quiet Time.

Set Stop Quiet Hour – Set the hour for Quiet Time to stop.

Set Stop Quiet Minute Set the minute for Quiet Time to stop.

Set Stop Quiet AM-PM Set AM or PM for the stop of Quiet Time.

Why should I use Quiet Time?

Quiet Time is used when there are park

rules or local regulations that prevent generators from running (sleep hrs.).

If there are no local rules or regulations, you may not want to use Quiet Time

– which would allow the generator to run at any time in a 24-hour period.
Where should I set Quiet Time? Set the Quiet Time start and stop settings

to coincide with local noise requirements, or for a specific time period that

you do not want the generator to automatically run each day.

Set Quiet Time Topoff This menu sets the time the generator will

autostart and run before Quiet Time starts. The generator will only

start on Quiet Time Topoff if the battery voltage (or battery SOC¹) start

parameter is within a specified range.
Default setting: Set Quiet Time Topoff = OFF
Range: OFF, 30-120 Minutes

What is Quiet Time Topoff and why should I use it? The Topoff feature

helps ensure the batteries have enough charge to last (i.e., prevent the inverter

from shutting down from a low battery condition) through the entire Quiet

Time period. When the Topoff feature is enabled by setting a time, the battery

voltage (or battery SOC¹) is monitored just before the start of Quiet Time;

and if required, the generator will automatically start to charge the batteries.

This Quiet Time Topoff menu allows you to set a time at which the generator

will autostart before Quiet Time starts. This applies whenever the start pa-

rameters are close to starting the generator at the start of Quiet Time. If the

battery voltage is within 0.3 volts² or less of reaching the 04A Gen Run VDC

start parameter, the generator will autostart. The Quiet Time Topoff feature

will also autostart the generator if the battery’s SOC is within 4% or less of

reaching the 04D Gen Run SOC start parameter¹.
Scenario example (Topoff based on battery voltage): The 04A Gen

Run VDC menu is set to start at 11.5 VDC, Quiet Time is set to start at

10PM, and the Quiet Time Topoff setting is 60 min. At 9PM, the battery

voltage reaches 11.8 VDC; because the Quiet Time Topoff feature is en-

abled (60 min.), the generator autostarts to allow the batteries to charge

for 60 minutes before Quiet Time turns the generator off.
Scenario example (Topoff based on battery SOC¹): The 04D Gen Run

SOC menu is set to start at 60%, Quiet Time is set to start at 10PM, and

the Quiet Time Topoff setting is 120 min. At 8PM, the battery SOC reaches

64%; because the Quiet Time Topoff feature is enabled (120 min.), the

generator autostarts to allow the batteries to charge for 120 minutes be-

fore Quiet Time turns the generator off.