7.0 Using an AGS Module

92

© 2012 Magnum Energy, Inc.

• Fault

MaxRn – The generator has turned off because the gen run

time—after autostarting—has exceeded the SETUP: 04F Max Gen Run

Time setting.

Info: The Max Gen Run Time menu uses the SETUP: 04B Gen Run

Time display to determine the generator’s run time. Cooldown and

warm-up times are not included in the Gen Run Time display.
Remedy: Confi rm that all the autostop parameters that are active

or enabled can be satisfi ed before the SETUP: 04F Max Gen Run

Time setting is reached.

If using the SETUP: 04A Gen Run VDC menu’s parameters:

– with a battery voltage setting to autostop, ensure the autos-

top voltage is less than the temperature-compensated absorb

charge voltage.
– with the “Float” setting to autostop, ensure the time that the

charger is in the Bulk Charge and Absorb Charge¹ stages is

shorter than the 04F Max Gen Run Time setting.
Refer to the SETUP: 04A Gen Run VDC section for additional

information on this setting.

• If

using

SETUP: 04B Gen Run Time, confi rm you have not set

the total run time (start time to the stop time) longer than the

SETUP: 04F Max Gen Run Time setting.

• If

using

SETUP: 04C Gen Run Amps, confi rm the inverter

load(s) that is used to determine the Stop Gen AC Amps set-

ting is not required to run longer than the SETUP: 04F Max Gen

Run Time setting.

• If

using

SETUP: 04D Gen Run SOC, confi rm that the METER:

04A BMK SOC reading is not “Think’n”, but shows an actual

percentage reading on the display (i.e., 85%), and the Stop

Gen SOC setting can be satisfi ed before the SETUP: 04F Max

Gen Run Time setting is reached.

• If

using

SETUP: 04E Gen Run Temp, the temperature around

the remote temperature sensor has not reached the Gen Run

Temp setting. You need to either lower the Gen Run Temp Start

setting, determine how to cool the area (remote temp sensor

location) to below the Gen Run Temp Start setting before the

04F Max Gen Run Time setting is reached, or increase the Max

Gen Run Time setting.

Lastly, confi rm that your warm-up and/or cooldown time when add-

ed to your autostop condition does not exceed the SETUP: 04F Max

Gen Run Time setting.
Info: Beginning with Revision 5.2 of the ME-AGS-N, the Max Gen Run

Time setting can be defeated. In some cases, it may be appropriate

to set the Max Gen Run Time setting to OFF. However, this feature is

mainly provided as a safety feature to ensure the generator doesn’t

run longer than the time it takes to reach the autostop conditions or

to expend the generator’s fuel capacity, whichever occurs fi rst – take

this into consideration if this setting is defeated.

Note¹: Several conditions determine the length of time that the charger is in the

Absorb Charge stage. Ensure the SETUP: 03E Absorb Done (Time, Amps, or SOC)

setting—determines when the Absorb Charge stage is complete and enters the

Float stage—is taken into account when setting the 04F Max Gen Run Time setting.