3 system status messages, 1 inverter mode status messages, 0 operation – Magnum Energy ME-ARC Remote User Manual

Page 58: Status message settings/info

Advertising
background image

52

© 2012 Magnum Energy, Inc.

5.0 Operation

FAULT

PWR

CHG

INV

Status Message

Settings/Info...

FAULT LED on:

See Section 5.3.4

CHG LED on:

See Section 5.3.2

Only INV LED on:

See Section 5.3.1

See appropriate section

to determine meaning

of message. If message

scrolls with secondary

screen message, refer

to Section 5.3.3.

Figure 5-2, System Status Screen (example)

5.3 System Status Messages

A status message may be an operational or fault message indicating the inverter/

charger’s current operating status. This section will cover the inverter/charger’s

operating and fault modes, and the available status messages under each mode.
Use the displayed status message and the status LED’s on your ME-ARC remote

(Figure 5-2) to determine the inverter/charger’s current operating status, and to

help troubleshoot the system if a fault occurs.
There are three modes of operation for the inverter/charger:
• Inverter mode • Charger mode • Fault mode
Refer to the appropriate section to locate information on any particular

status message.

5.3.1 Inverter Mode Status Messages

There are several Inverter mode messages. View the top line of the LCD

display and the corresponding message in this section to determine and

understand the particular Inverter mode.
• Inverting – The inverter is providing AC voltage on its output by

inverting power from the batteries.
• Inverter

Standby

The inverter is on but not actively providing power.

However, the inverter remains active and an external AC power (utility or

generator) is passing through the inverter to power the AC loads.
• No Inverter Comm – The remote is no longer receiving any

communication data via the Magnum Network.

Remedy: Reset the remote by disconnecting the remote commu-

nications cable from the inverter for fi ve seconds, and then recon-

nect (see Figure 2-2). If the fault continues, fi rst check/replace the

remote cable (4-wire telephone cable).

What if the cable is not the issue?

Try another remote display

Reconnect the remote from the Remote port to the Network port

The inverter may need servicing

• Off

– This message tells you that there is no AC available on the

inverter’s AC output. The inverter function is OFF and there is no utility or

generator AC power sensed on its input.
• Searching – The inverter is in Search mode. This means the AC loads

on the inverter output are less than the SETUP menu’s 02A Search Watts

setting. The Search mode function is used to reduce the inverter draw from

the battery, and may be turned off at any time if you want full inverter

output voltage available at all times (see 02 Invert Setup on page 23).