0 using an ags module – Magnum Energy ME-ARC Remote User Manual

Page 93

Advertising
background image

© 2012 Magnum Energy, Inc.

87

7.0 Using an AGS Module

Table 7-2, AGS Remote Operational Statuses (cont.)

STATUS

DESCRIPTION

Quiet Time

The AGS has entered Quiet Time per the SETUP: 04G

Quiet Time setting.

Note: The generator will not autostart during Quiet Time.
Ready

The CTRL: 03 Gen Control menu is set to AUTO, and the

AGS is ready to automatically start the generator based

on the active autostart settings under the SETUP: 04

AGS Setup menu.

STATUS

DESCRIPTION

Start Amp

The generator has started based on the SETUP: 04C

Gen Run Amps setting.

Start Exercise The generator has started based on the SETUP: 04H

Gen Exercise setting.

Start SOC

The generator has started based on the SETUP: 04D

Gen Run SOC setting.

Start Temp

The generator has started based on the SETUP: 04E

Gen Run Temp setting.

Start Test

The AGS is in Test mode. Test mode may be started

from the TEST button located on the AGS,

Start Time

The generator has started based on the SETUP: 04B

Gen Run Time setting.

Start Topoff

The generator has started based on the SETUP: 04G

Quiet Time Topoff Time setting.

Start VDC

The generator has started based on SETUP: 04A Gen

Run VDC setting.

7.7.2 AGS Remote Start Statuses

The following “Start” statuses identify the condition that autostarted the

generator. If you determine that the autostart condition occurred sooner

than expected (or didn’t want this autostart condition), refer to the Setup

section for your specifi c remote to change (or defeat) the autostart setting.

Table 7-3, AGS Remote Start Statuses

Advertising