3.0 Setup

03B Battery Type – Used to select the battery type, which determines

the battery charge profi le and ensures the batteries are receiving the

proper charge voltage. The fi xed voltage selections are GEL (for Gel

batteries), Flooded (for liquid lead acid batteries), AGM 1 (for Lifeline

AGM batteries), and AGM 2 (for East Penn/Deka/Discover/Trojan

AGM batteries).

The Custom selection allows the Float, Absorb, and

Equalization charge voltage settings to be individually adjusted. S

ee

Table 3-2 to determine the specifi c charge voltage based on the battery

type selected.
Default setting: Battery Type = Flooded
Range: GEL, Flooded, AGM1, AGM2, Custom

Info: The voltage settings shown in Table 3-2 are based on the Bat-

tery Temperature Sensor (BTS) at a temperature of 77° F (25° C), or

not connected. If the BTS is connected, the actual charge voltage will

increase if the temperature around the BTS is below 77° F (25° C), and

decrease if higher than 77° F (25° C). This ensures the batteries re-

ceive the correct charge voltage regardless of temperature.

• 03C Max Charge Rate Sets the maximum charge rate allowed

to charge the batteries during Bulk, Absorption, Float, and Equalize

charging. Selections are Max Charge = 0% up to 100%. The Max Charge

= 0% setting is available to help minimize charging while continuing

to allow pass-thru power. The rest of the selections are provided to

limit the charge rate to the battery bank, which helps prevent battery

overheating caused by charging at too high a charge rate.
The Max Charge Rate selections are provided as a percentage of the

inverter/charger’s maximum charging capability. Refer to the label on

the side of the inverter (or owner’s manual) to determine the inverter’s

maximum charge rate. Once you fi nd this max charge rate, determine

the percentage needed to limit the charge rate to your battery bank.
Default setting: Max Charge = 100%
Range: 0-100%

Info: If you are supplying two AC sources (utility and generator) to

the inverter’s single input through an AC transfer switch, adjust the

AC Input Amps setting to the smaller AC circuit breaker size of the

two AC sources.
Info:
The AC Input Amps setting is dependent on the stability of the

AC source. If using a generator, factors such as altitude and output

voltage regulation may require a lower setting than the generator’s

circuit breaker size. For best performance, lower the AC Input Amps

setting to 1/3 of the generator’s rated capacity, and then while the

generator is heavily loaded, gradually increase the setting as high

as possible, but ensure the voltage level stays above the 03D VAC

Dropout setting.
CAUTION: Unless you have an MS Hybrid Series inverter/charger—

which provides the Load Support feature—the AC Input Amps setting

does not limit the current to the inverter loads. If the current from

the loads on the output of the inverter are greater than the circuit

breaker rating on the incoming AC source, you may experience

nuisance tripping on this breaker.