Setup: 02 invert setup, 0 setup – Magnum Energy ME-ARC Remote User Manual

Page 29

Advertising
background image

© 2012 Magnum Energy, Inc.

23

3.0 Setup

• 01B

Contrast

– This setting enables you to adjust the contrast of the

LCD screen based on the current lighting conditions and viewing angle.
Default setting: Contrast = 100%
Range: 0-100%

• 01C

Backlight

– This setting enables you to adjust the backlight of the

LCD screen based on the current lighting conditions and viewing angle.
Default setting: Backlight = 50%
Range: 0-100%

• 01D Power Save – This setting enables you to turn off the Power

Save feature, or to select the time that determines when the display

goes into Power Save mode.
Default setting: PwrSave = 15 minute
Range: OFF, 1, 5, 10, 15, 30, 45, 60 Min

What is the Power Save feature? The Power Save feature turns off the

LCD backlight and the LED’s on the remote to conserve energy. The remote

goes into Power Save mode if there hasn’t been a button press or fault

message for a period of time (this time is determined by the 01D Power Save

setting). Whenever the remote goes into the Power Save mode, the LCD

backlight and the LED’s can be reactivated by pressing any button. If you

have a fault during the Power Save mode, the LCD backlight and the FAULT

LED will come on and stay on as long as the fault is present.

Info: If you want the LCD backlight and the LED’s to always be on,

you will need to turn the Power Save feature off by selecting OFF

from the Set Power Save menu.

01E Temp Display – This menu item selects whether to display tempera-

tures in Fahrenheit or Celsius. Once you select either Fahrenheit or Celsius,

the following menu items will use your selection: the METER button’s 03D

AGS Temp menu, the SETUP button’s 04E Gen Run Temp menu, and the

TECH button’s 01 Temperatures menu.
Default setting: Fahrenheit
Range: Fahrenheit, Celsius

SETUP: 02 Invert Setup
The following menus are used to set up those functions that are only related

to the Inverting mode of the inverter/charger.

02A Search Watts – Allows you to turn off the Search Watts feature, or

to adjust the power level to determine when the inverter leaves Search

mode. If this feature is not needed, select Search=OFF. When search is

turned off, the inverter continuously provides full AC voltage to the loads.
Default setting: 5 Watts
Range: OFF, 5-50 Watts

Info: When the Search Watts feature is active, “Searching” ap-

pears on the top line of the LCD display and the green INV LED will

slowly fl ash.

What is the Search Watts feature? This feature is used to help save

battery power by reducing the inverter’s output to search pulses when there

is no detectable load. If a load greater than the wattage level setting turns on

while the inverter is ‘searching’, the inverter will start ‘inverting’ to provide

full voltage on its output.

Advertising