3.0 Setup

Set Final Charge Stage = Silent Silent mode stops charging once it

transitions from Absorb mode to ‘Silent’. Once the charger enters Silent

mode the battery voltage is continuously monitored. If the batteries

fall to the Set DC Volts to Rebulk value, the charger restarts the Bulk

Charge mode and then transitions to Absorb Charge mode. After the

Absorb Charge mode, the charger again transitions to Silent mode. This

silent to rebulk to absorb and back to silent cycle will continue as long

as it is required.
Set DC Volts to ReBulk – When Silent mode is selected, you must

also set the DC voltage set-point where the charger restarts the Bulk

Charge mode. This setting should be at the lowest DC volts you want the

batteries to fall before starting a new bulk charge. Typically, the lowest

DC volts the batteries are allowed to fall is 12.0 to 12.2 VDC (12-volt

systems), 24.0 to 24.4 VDC (24-volt systems), and 48.0 to 48.8 VDC

(48-volt systems) respectively.
Default setting: Set DC Volts to ReBulk = 12.0
Ranges: 12.0-16.0 VDC (12v), 24.0-32.0 VDC (24v), 48.0-64.0 VDC (48v)
Why should I use the Silent Stage? Silent mode is typically used when

an alternate charge source is available and able to fully charge or fi nish

the charge cycle after the Absorb stage. A major difference between

Multi mode and Silent mode is that the Silent mode returns to Bulk mode

instead of Float mode. In Silent mode you can also adjust the Rebulk

set-point in order to allow the alternate charge source to provide more

of the battery charging.