10. P.C. BOARD EXCHANGE PROCEDURES

10-1. Exchange of P.C. Board for Indoor Service

Part code

431-6V-269

Model type

MMU-AP

✻✻

✻✻

✻✻

✻✻

✻✻

1H series

MMU-AP

✻✻

✻✻

✻✻

✻✻

✻✻

1MH series

MMC-AP

✻✻

✻✻

✻✻

✻✻

✻✻

1H series

MMK-AP

✻✻

✻✻

✻✻

✻✻

✻✻

1H series

MMD-AP

✻✻

✻✻

✻✻

✻✻

✻✻

1SPH/SH series

MMU-AP

✻✻

✻✻

✻✻

✻✻

✻✻

2SH series

P.C. board model

MCC-1402

Label display on P.C. board

03DD M05

Requirement at exchange of P.C. board assembly for indoor service

Before exchange, in the fixed memory (hereinafter EEPROM, IC10) installed on the indoor P.C. board, the type
exclusive to the model and the capacity code are stored at shipment from the factory. The important setup data
such as line/indoor/group address which are set up (Auto/Manual) or high ceiling exchange setup at installation
time, respectively.

Proceed with exchange of P.C. board assembly for indoor service in the following procedure.

After exchange work, check again the setup for indoor unit No. or group header/follower units to confirm whether
the setup contents are correct or not, and then check also the refrigerant circuit system by a test operation, etc.

<Exchange procedure>

Method 1

Before exchange, it is possible to turn on power of the indoor unit and read out the setup
contents from the wired remote controller.

Readout of EEPROM data: Procedure 1

ò

Exchange of P.C. board for service & power ON: Procedure 2

ò

Writing-in of the readout EEPROM data: Procedure 3

ò

Power supply reset (All the indoor units connected to the remote controller in case of group operation control)