Check code

[F04]

Check code name

TD1 sensor error

Cause of operation

TD1 sensor Open/Short

This error code means detection of Open/Short of TD1 sensor. Check disconnection of circuit for connection of
connector (TD1 sensor: CN502, White) and characteristics of sensor resistance value.
(Refer to Outdoor unit temperature sensor characteristics.)
If sensor is normal, replace outdoor I/F P.C. board.

Check code

[F05]

Check code name

TD2 sensor error

Cause of operation

TD2 sensor Open/Short

This error code means detection of Open/Short of TD2 sensor. Check disconnection of circuit for connection of
connector (TD2 sensor: CN503, Pink) and characteristics of sensor resistance value.
(Refer to Outdoor unit temperature sensor characteristics.)
If sensor is normal, replace outdoor I/F P.C. board.

Check code

[F06]

Check code name

TE1 sensor error

Cause of operation

TE1 sensor Open/Short

This error code means detection of Open/Short of TE1 sensor. Check disconnection of circuit for connection of
connector (TE1 sensor: CN505, Green) and characteristics of sensor resistance value.
(Refer to Outdoor unit temperature sensor characteristics.)
If sensor is normal, replace outdoor I/F P.C. board.

Check code name

[F07]

Check code name

TL sensor error

Cause of operation

TL sensor Open/Short

This error code means detection of Open/Short of TL sensor. Check disconnection of circuit for connection of connec-
tor (TL sensor: CN521, White) and characteristics of sensor resistance value.
(Refer to Outdoor unit temperature sensor characteristics.)
If sensor is normal, replace outdoor I/F P.C. board.

Check code name

[F08]

Check code name

TO sensor error

Cause of operation

TO sensor Open/Short

This error code means detection of Open/Short of TO sensor. Check disconnection of circuit for connection of
connector (TO sensor: CN507, Yellow) and characteristics of sensor resistance value.
(Refer to Outdoor unit temperature sensor characteristics.)
If sensor is normal, replace outdoor I/F P.C. board.

Check code name

[F10]

Check code name

Indoor TA sensor error

Cause of operation

TA sensor Open/Short

This error code means detection of Open/Short of TA sensor. Check disconnection of circuit for connection of connec-
tor (TA sensor: CN104, Yellow) and characteristics of sensor resistance value. (Refer to Outdoor unit temperature
sensor characteristics.)
If sensor is normal, replace indoor P.C. board.

Check code name

[F12]

Check code name

TS sensor error

Cause of operation

TS1, TS2 sensor Open/Short

This error code means detection of Open/Short of TS sensor. Check disconnection of circuit for connection of
connector (TS1 sensor: CN504, White TS2 sensor: CN522, Black) and characteristics of sensor resistance value.
(Refer to Outdoor unit temperature sensor characteristics.)
If sensor is normal, replace outdoor I/F P.C. board.

Auxiliary code : 01: TS1 sensor 02 : TS2 sensor

Check code name

[F13]

Check code name

TH sensor error

Cause of operation

IGBT built-in sensor error in A3-IPDU

Auxiliary code : 01: Compressor 1 side 02: Compressor 2 side

This error code means IGBT built-in temperature sensor error.
Check connection of connectors CN06 on IPDU P.C. board and CN600 on I/F P.C. board.
If sensor is normal, replace IPDU P.C. board.